EVALUATION OF FIELD AGED CROSS-LINKED POLYETHYLENE CABLES BY PARTIAL DISCHARGE LOCATION

被引:13
作者
MASHIKIAN, MS
LUTHER, R
MCIVER, JC
JURCISIN, J
SPENCER, PW
机构
[1] GE CO,DEPT POWER SYST ENGN,SCHENECTADY,NY 12345
[2] PUBL SERV ELECT & GAS CO,DEPT ELECT DISTRIBUT,NEWARK,NJ 07101
[3] FLORIDA POWER CORP,ST PETERSBURG,FL
关键词
D O I
10.1109/61.296237
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Partial discharge sites were located in several field aged crosslinked polyethylene insulated medium voltage cables, using a newly developed instrument. Subsequent AC breakdown tests indicated that, with partial discharge inception voltages lower than 3 times operating voltage, the failures occurred at the partial discharge sites. In all cases, the failures originated at the sites of long water trees which affected the cables at discrete locations rather than uniformly over their entire lengths. Attributes of a partial discharge locator capable of performing in-situ non-destructive diagnostic tests on cables are discussed and field application procedures are described.
引用
收藏
页码:620 / 628
页数:9
相关论文
共 19 条
[1]   DEGRADATION OF POLYMERIC INSULATION DUE TO PHOTOEMISSION CAUSED BY HIGH ELECTRIC-FIELDS [J].
BAMJI, SS ;
BULINSKI, AT ;
DENSLEY, RJ .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1989, 24 (01) :91-98
[2]  
BARTNIKAS R, 1988, IEEE T POWER DELIVER, V3
[3]  
BARTNIKAS R, 1979, STP669 ASTM
[4]   A NEW METHOD FOR DETECTION AND LOCATION OF DISTRIBUTED PARTIAL DISCHARGES (CABLE FAULTS) IN HIGH-VOLTAGE CABLES UNDER EXTERNAL INTERFERENCE [J].
BEYER, M ;
KAMM, W ;
BORSI, H ;
FESER, K .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (09) :3431-3438
[5]  
BULINSKI AT, 1988, 1988 IEEE INT S EL I
[6]  
COSTELLO DA, 1967, IEEE T POWER APPARAT, V86, P23
[7]  
DU Z, 1992, NOV P INT C DSP APPL
[8]  
HARTLEIN RA, 1989, IEEE T POWER DELIVER, V4
[9]   BETTER SURGE PROTECTION EXTENDS URD CABLE LIFE [J].
HOPKINSON, RH .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (10) :2827-2835
[10]   SIGNAL-PROCESSING TECHNIQUES FOR PARTIAL DISCHARGE SITE LOCATION IN SHIELDED CABLES [J].
KNAPP, CH ;
BANSAL, R ;
MASHIKIAN, MS ;
NORTHROP, RB .
IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (02) :859-865