TRENDS IN ACTIVE POWER-LINE CONDITIONERS

被引:367
作者
AKAGI, H
机构
[1] Department of Electrical Engineering, Okayama University, Okayama-city
关键词
D O I
10.1109/63.311258
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Active power line conditioners, which are classified into shunt and series ones, have been studied with the focus on their practical installation in industrial power systems. In 1986, a combined system of a shunt active conditioner of rating 900 kVA and a shunt passive filter of rating 6600 kVA was practically installed to suppress the harmonics produced by a large capacity cycloconverter for steel mill drives. More than one hundred shunt active conditioners have been operating properly in Japan. The largest one is 20 mVA, which was developed for flicker compensation for an are furnace with the help of a shunt passive filter of 20 mVA. In this paper, the term of ''active power line conditioners'' would be used instead of that of ''active power filters'' because active power line conditioners mould cover a wider sense than active power filters. The primary intent of this paper is to present trends in active power line conditioners using PWM inverters, paying attention to practical applications.
引用
收藏
页码:263 / 268
页数:6