UTILITY CAPACITOR SWITCHING AND ADJUSTABLE-SPEED DRIVES

被引:15
作者
WAGNER, VE
STANIAK, JP
ORLOFF, TL
机构
[1] Detroit Edison, Detroit, MI
关键词
D O I
10.1109/28.85477
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Surges of less than 200% magnitude caused by utility capacitor bank switching can disrupt operation of adjustable-speed drives. PWM drives are more sensitive to surges because the drive transitors have lower overvoltage tolerance than SCR drives. This paper uses the results of a case study to analyze the circumstances of drives tripped by utility capacitor switching. It is shown that low loss utility capacitors increase the surge magnitude by decreasing system damping. Surge magnification is possible at buses remote from the capacitor, and the three conditions for magnification are described. It is also shown that drive sensitivity to the surge depends on whether the drive filter inductor is saturated by the surge.
引用
收藏
页码:645 / 651
页数:7
相关论文
共 13 条
[1]  
CONRAD L, 1989, MAY C REC IND COMM P, P74
[2]  
KEY TS, 1979, IEEE T IND APPL, V1, P381
[3]  
MARTZLOFF FD, 1986, IEEE T IND APPL, V1, P634
[4]  
PLANZ HM, 1973, IEEE T POWER APP SYS, V92, P907
[5]  
SCHLUETER RA, 1989, P BULK POWER SYST VO
[6]  
SCHULTZ AJ, 1959, IEEE T POWER APPARAT, V77, P1418
[7]  
Van Sickle R. C., 1954, AIEE T, V73, P971
[8]  
VILCHECK WS, 1986, IEEE IND COMM POWER
[9]  
ZABORSZKY J, 1963, AIEE T POWER APP SYS, V81, P815
[10]   MOVING POWER THROUGH THE NORTHEAST CORRIDOR [J].
ZORPETTE, G .