VECTOR ANALYSIS AND CONTROL OF ADVANCED STATIC VAR COMPENSATORS

被引:569
作者
SCHAUDER, C [1 ]
MEHTA, H [1 ]
机构
[1] ELECT POWER RES INST,PALO ALTO,CA 94303
关键词
INVERTERS; POWER TRANSMISSION; STATIC VAR COMPENSATORS;
D O I
10.1049/ip-c.1993.0044
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The advanced static VAR compensator (now widely known as the static condenser or STATCON) uses a high power self-commutating inverter to draw reactive current from a transmission line. Two fundamentally different types of invertor can be used for this purpose, one providing control of output voltage magnitude and phase angle, and the other having only phase angle control. For each of these types, the governing equations are derived, and frequency domain analysis is used to obtain the relevant transfer functions for control system synthesis. Further analysis is provided to determine the response of the STATCON to negative sequence and harmonic voltage components on the transmission line. The results are illustrated with measured waveforms obtained from a scaled analogue model of an 80 MVAR STATCON.
引用
收藏
页码:299 / 306
页数:8
相关论文
共 6 条
  • [1] EDWARDS CW, 1988, WIN IEEE PES POW M
  • [2] GYUGYI L, CIGRE23203 PAP
  • [3] Hingorani N.G., 1988, P AM POW C US, V50
  • [4] LYON MV, 1954, TRANSIENT ANAL ALTER
  • [5] PARK RH, 1928, GENERAL ELECTRIC REV, V31
  • [6] RP30231 EL POW RES I