CHARGING CURRENT DATA FOR GUESSWORK-FREE DESIGN OF HIGH-RESISTANCE GROUNDED SYSTEMS

被引:39
作者
BAKER, DS
机构
[1] Central Engineering Division, Brown & Root, Inc., Houston
关键词
D O I
10.1109/TIA.1979.4503628
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The design of high-resistance grounded power systems requires the sizing of the grounding resistor to provide a current flow equal to or greater than three times the system charging current (Ico) of each phase. In industrial power systems the insulated power cables are a major source of system charging current which flows into line-to-ground faults. Data are presented which will allow cable charging currents to be quickly and precisely determined after the cable size, voltage, footage, insulation type, and thickness have been determined. Charging current data for transformers, motors, generators, and capacitors are also included. Copyright © 1979 by The Institute of Electrical and Electronics Engineers, Inc.
引用
收藏
页码:136 / 140
页数:5
相关论文
共 16 条