DESIGN, IMPLEMENTATION AND TESTING OF A MICROPROCESSOR-BASED HIGH-SPEED RELAY FOR DETECTING TRANSFORMER WINDING FAULTS

被引:55
作者
SIDHU, TS
SACHDEV, MS
WOOD, HC
NAGPAL, M
机构
[1] Power System Research Group, University of Saskatchewan, Saskatoon
关键词
POWER SYSTEM PROTECTION; TRANSFORMER PROTECTION; MICROPROCESSOR-BASED RELAYS; DIGITAL ALGORITHMS;
D O I
10.1109/61.108896
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the design, implementation and testing of a microprocessor-based high-speed relay that correctly detects transformer winding faults. Instead of relying on the presence of harmonics to identify magnetizing inrush, it uses a non-linear model of the transformer to determine the state of its health. One version of the relay is suitable for protecting single-phase transformers, whereas another version is for protecting three-phase transformers. A three-phase delta-wye 15 kVA transformer was used to test the relay for a variety of operating conditions. The results show that the relay performs well.
引用
收藏
页码:108 / 117
页数:10
相关论文
共 6 条
[1]  
MAYER WS, 1983, ELECTROMAGNETIC TRAN
[2]   A DIGITAL RELAYING ALGORITHM FOR DETECTING TRANSFORMER WINDING FAULTS [J].
SACHDEV, MS ;
SIDHU, TS ;
WOOD, HC .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (03) :1638-1648
[3]  
SACHDEV MS, 1988, EH02691PWR PUBL
[4]  
SACHDEV MS, 1979, 79EH01487PWR PUBL
[5]  
SIDHU TS, 1989, 4TH INT C DEV POW SY
[6]  
1976, APPLIED PROTECTIVE R