REVIEW OF CHEMICAL INDICATORS OF DEGRADATION OF CELLULOSIC ELECTRICAL PAPER INSULATION IN OIL-FILLED TRANSFORMERS

被引:276
作者
EMSLEY, AM [1 ]
STEVENS, GC [1 ]
机构
[1] NATL POWER RES & TECHNOL,LEATHERHEAD KT22 7SE,SURREY,ENGLAND
关键词
CHEMICAL INDICATORS; CONDITION MONITORING; DEGRADATION; ELECTRICAL INSULATION; LIFE PREDICTION; POWER TRANSFORMERS; 2-FURALDEHYDE;
D O I
10.1049/ip-smt:19949957
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Chemical and thermal degradation of electrical insulation in oil-filled transformers, mechanisms of failure and methods of condition monitoring and of life prediction are reviewed. An insulation life prediction model is developed and estimates of insulation life are presented under a variety of oil/paper conditions. Systematic measurements of the concentration of chemical indicators in transformer oil are used to demonstrate that furaldehyde and related products can be used to detect high rates of paper degradation. Similarly, phenol and related products indicate electrical degradation in phenol-formaldehyde resins.
引用
收藏
页码:324 / 334
页数:11
相关论文
共 76 条
[1]  
ACKER CR, 1976, IEEE POWER ENG SOC M, P76
[2]  
BARRACLOUGH B, 1973, P C DIAGNOSTIC TESTI, P178
[3]  
BAUGH KD, BIOTECHNOL BIOENG, V31, P50
[4]  
Blazej A., 1985, CELLULOSE ITS DERIVA
[5]  
Bouvier B., 1970, Revue Generale de l'Electricite, V79, P489
[6]  
BRUMMET BD, 1964, INSULATION, V10, P35
[7]  
Burton P. J., 1984, P CIGRE INT C LARGE, p1~10
[8]  
BURTON PJ, 1984, INT C LARGE HV ELECT
[9]  
BURTON PJ, 1988, P ICGRE C PARIS
[10]   PYROLYSIS OF CELLULOSE AND ACTION OF FLAME-RETARDANTS .2. FURTHER ANALYSIS AND IDENTIFICATION OF PRODUCTS [J].
BYRNE, GA ;
GARDINER, D ;
HOLMES, FH .
JOURNAL OF APPLIED CHEMISTRY, 1966, 16 (03) :81-+