FREQUENCY-RESPONSE METHODS FOR TUNING STABILIZERS TO DAMP OUT TIE-LINE POWER OSCILLATIONS - THEORY AND FIELD-TEST RESULTS

被引:22
作者
BOLLINGER, KE [1 ]
WINSOR, R [1 ]
CAMPBELL, A [1 ]
机构
[1] CALGARY POWER LTD,CALGARY,ALBERTA,CANADA
来源
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS | 1979年 / 98卷 / 05期
关键词
D O I
10.1109/TPAS.1979.319463
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
During the past ten years a number of authors have put forward techniques for tuning power system stabilizers (PSS) in the literature. Some of these techniques have been tested in on-site applications and others have been evaluated using simulation techniques. This paper describes a theoretical basis, and supporting experimental evidence from tests performed at a power plant, for tuning power system stabilizers using frequency response techniques. By using the method described in this paper, the power system analyst is able to obtain an approximate measure of the amount of damping that can be expected from the stabilizer in damping out tie-line power oscillations. The tests were conducted on the intertie between the Alberta and British Columbia Hydro power pools. Test results indicated a direct correlation between the improvement in the electric power damping as observed by field tests and that predicted by theoretical means. Although the method suggested in this paper has general application to power system stabilization for local mode damping and intertie damping it was applied to the specific case where the tie-line power was used as a feedback signal to the stabilizer. Copyright © 1979 by The Institute of Electrical and Electronics Engineers. Inc.
引用
收藏
页码:1509 / 1515
页数:7
相关论文
共 9 条
[1]  
BOLLINGER KE, IEEE T PAS, V94, P1484
[2]  
DANDENO PL, 1976, CEA J, V1
[3]   OPTIMAL OUTPUT FEEDBACK CONTROL OF A SYNCHRONOUS MACHINE [J].
DAVISON, EJ ;
RAU, NS .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1971, PA90 (05) :2123-+
[4]  
EVELEIGH VW, 1972, INTRO CONTROL SYSTEM
[5]   MODELING AND TESTING OF VALLEY STEAM PLANT SUPPLEMENTAL EXCITATION CONTROL-SYSTEM [J].
HAYES, DR ;
CRAYTHORN, GE .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1973, PA92 (02) :464-470
[6]  
RAINA VM, IEEE T PAS, V95, P667
[7]   ALINEMENT AND MODELING OF HANFORD EXCITATION CONTROL FOR SYSTEM DAMPING [J].
WARCHOL, EJ ;
SCHLEIF, FR ;
GISH, WB ;
CHURCH, JR .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1971, PA90 (02) :714-&
[8]  
WINSOR RA, 1977 IEEE SUMM POW M
[9]  
WINSOR RA, 1977, MAR SPRING M CAN EL