PARTICLE CONTAMINATION OF HIGH-VOLTAGE DC INSULATORS BELOW CORONA THRESHOLD

被引:29
作者
HORENSTEIN, MN
MELCHER, JR
机构
[1] Massachusetts Institute of Technology Cambridge, Massachusetts
来源
IEEE TRANSACTIONS ON ELECTRICAL INSULATION | 1979年 / 14卷 / 06期
关键词
D O I
10.1109/TEI.1979.298185
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A scaled dc transmission line insulator string has been implemented in sub-corona experiments to identify parameters important to the particle contamination process. Simple trajectory analysis of particle motion yields good agreement between predicted contamination features and observed phenomena, and suggests a model for the quantitative prediction of contamination of dc insulators on actual transmission lines in the field. The deposition rate on surfaces that become contaminated is experimentally shown to be given by the average product of particle mobility, particle mass density in the ambient air, and normal electric field on the insulator surface. Copyright © 1979 by The Institute of Electrical and Electronics Engineers, Inc.
引用
收藏
页码:297 / 305
页数:9
相关论文
共 11 条
[1]  
ANNESTRAND A, 1967, DIRECT CURR, V12, P1
[2]  
HAERER H, 1971, THESIS U STUTTGART
[3]  
HIRSCH F, 1975, PAS, V94, P45
[4]  
HORENSTEIN MN, 1978, THESIS MIT
[5]  
KIMOTO J, 1973, PAS, V92, P943
[6]  
OLSEN R, 1978, FEB IEEE WINT POW M
[7]  
ROSE HE, 1965, ELECTROSTATIC PRECIP, P138
[8]   INITIATION OF DRY BANDS ON POLLUTED INSULATION [J].
SALTHOUSE, EC .
PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1968, 115 (11) :1707-+
[9]   CHARGE SIMULATION METHOD FOR CALCULATION OF HIGH-VOLTAGE FIELDS [J].
SINGER, H ;
STEINBIGLER, H ;
WEISS, P .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1974, PA93 (05) :1660-1668
[10]  
WHITE H, 1963, IND ELECTROSTATIC PR, P64