EXPERIMENTAL INVESTIGATION OF PERFORMANCE OF A RESIDENTIAL AIR-CONDITIONING SYSTEM WITH AN EVAPORATIVELY COOLED CONDENSER

被引:31
作者
GOSWAMI, DY
MATHUR, GD
KULKARNI, SM
机构
[1] Solar Energy and Energy Conversion Laboratory, Mechanical Engineering Department, University of Florida, Gainesville, FL
来源
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME | 1993年 / 115卷 / 04期
关键词
D O I
10.1115/1.2930051
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents an experimental investigation of the use of indirect evaporative cooling process to increase the performance of an air-to-air vapor compression refrigeration system. The condenser of an existing 2.5 ton (8.8 kW) air conditioning system at the University of Florida's Energy Park in Gainesville was retrofitted with a media pad type evaporative cooler a water source, and a pump. The system performance was monitored without and with the evaporative cooler on the condenser The data show that electric energy savings of 20 percent can be achieved by using an evaporatively cooled air condenser The energy savings can pay for the cost associated with retrofitting the condenser in as little as two years.
引用
收藏
页码:206 / 211
页数:6
相关论文
共 14 条
[1]  
BROWN WK, 1990, ASHRAE TRAN, V96, P1227
[2]  
Kline S.J., 1953, MECH ENG, P3
[3]  
MATHUR GD, 1990, ASHRAE TRAN, V96, P1241
[4]  
MATHUR GD, 1990, NOV ASME S THERM HYD, V5, P79
[5]  
MCDONALD GW, 1990, ASHRAE TRAN, V96, P1236
[6]  
MEKLER G, 1990, CONSULTING SPECIFYIN, P90
[7]  
SCOFIELD C, 1992, ASHRAE T JUN, P49
[8]  
Scofield CM., 1986, ASHRAE T, V92, P371
[9]  
SCOFIELD CM, 1986, ASHRAE J OCT
[10]  
Woolridge M.J., 1976, ASHRAE T, V82, P146