ASSOCIATIONS BETWEEN TYPE OF VENTILATION AND AIR-FLOW RATES IN OFFICE BUILDINGS AND THE RISK OF SBS-SYMPTOMS AMONG OCCUPANTS

被引:56
作者
SUNDELL, J [1 ]
LINDVALL, T [1 ]
STENBERG, B [1 ]
机构
[1] KAROLINSKA INST,INST ENVIRONM MED,S-10401 STOCKHOLM 60,SWEDEN
关键词
D O I
10.1016/0160-4120(94)90141-4
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The association between type of ventilation and outdoor-air flow rates and Sick Building Syndrome (SBS) and SBS symptoms was studied in a cross-sectional questionnaire and field study comprising 160 office buildings, and 260-2649 respondents with case-controls as well as prevalence comparisons. Measured ventilation rates were higher than required by most building codes and consisted of fresh-air (outdoor-air) inflow of 17 +/- 14 L/p and 2.0 +/- 1.3 air changes/h. Increased risk of SBS and elevated prevalence of general SBS symptoms were associated with low outdoor-air flow rates, presence of copying machines in office rooms, and ventilation operating hours was less than 10 h/d. There was a suspected association between SBS and air humidification, recirculation of exhaust air at high outdoor-air flow rates but not at low outdoor-air flow rates, and with natural or mechanical exhaust ventilation systems. SBS was not associated with the presence of a rotary heat exchanger or with the supply air temperature higher than the room air temperature.
引用
收藏
页码:239 / 251
页数:13
相关论文
共 41 条
[1]  
Andersson, Andersson, Sundell, Zingmark, Mass transfer of contaminants in rotary enthalpy exchangers, Indoor Air, 3, pp. 143-148, (1993)
[2]  
ASHRAE, ASHRAE Standard 62–73. Standards for natural and mechanical ventilation, (1977)
[3]  
ASHRAE, ASHRAE Standard 62–1981, Ventilation for Acceptable Indoor Air Quality, (1981)
[4]  
ASHRAE, ASHRAE Standard 62–1989, Ventilation for Acceptable Indoor Air Quality, (1989)
[5]  
Bakke, Levy, Indoor air quality in kindergartens - relation to health effects, Proc. Indoor Air '90, 1, pp. 3-8, (1990)
[6]  
Burge, Jones, Robertson, Sick building syndrome, Proc. Indoor Air '90, 1, pp. 479-483, (1990)
[7]  
Eriksson, Hoog, The office illness project in northern Sweden. The significance of psychosocial factors for the prevalence of the “sick building syndrome”. A case referent study, Proc. Indoor Air '93, 1, pp. 333-337, (1993)
[8]  
Fanger, Introduction of the olf and the decipol units to quantify air pollution perceived by humans indoors and outdoors, Energy Build., 12, pp. 1-6, (1988)
[9]  
Fanger, Lauridsen, Bluyssen, Clausen, Air pollution sources in offices and assembly halls, quantified by the olf unit, Energy Build, 12, pp. 7-19, (1988)
[10]  
Fisk, Faulkner, Prill, Air exchange effectiveness of conventional and task ventilation for offices, Proc. Indoor Air Quality '91 Healthy Buildings, pp. 30-34, (1991)