EVALUATION METHODOLOGY FOR SEISMIC BASE-ISOLATION OF NUCLEAR EQUIPMENTS

被引:4
作者
EBISAWA, K
UGA, T
机构
[1] Japan Atomic Energy Research Institute, Naka-gun, Ibaraki-ken, 319-11, Tokai-mura
关键词
D O I
10.1016/0029-5493(93)90210-Z
中图分类号
TL [原子能技术]; O571 [原子核物理学];
学科分类号
0827 ; 082701 ;
摘要
An evaluation methodology for seismic base isolated nuclear equipments is proposed. The evaluation can be classified into two steps. In the first step, the seismic functional failure probability during the lifetime of equipment without base isolation devices is quantified in order to decide the applicability of the base isolated structure. The second step is comparative and calculates the ratio of the seismic failure frequency of the equipment without base isolation devices to that with them in order to evaluate the effectiveness of the base isolated structure. The sample evaluation considers the case of high voltage type emergency transformer with ceramic tubes.