EFFECT OF OIL VISCOSITY ON TRANSFORMER LOADING CAPABILITY AT LOW AMBIENT-TEMPERATURES

被引:27
作者
AUBIN, J [1 ]
PIERCE, LW [1 ]
LANGHAME, Y [1 ]
机构
[1] GE,ROME,GA
关键词
D O I
10.1109/61.127044
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The applicability of the ANSI loading guide for power transformers is limited to ambient temperatures above 0-degrees-C because the thermal model does not account for variations in the oil viscosity and winding resistance. A practical calculation method has been developed based on the bottom-oil temperature and the surface temperature at the top of the cooling duct. Results indicate that the proposed thermal model could provide a sound basis for calculating the overload capacity for ambient temperatures below 0-degrees-C or for severe overloads of short duration.
引用
收藏
页码:516 / 524
页数:9
相关论文
共 12 条
[1]  
AUBIN J, 1981, CEA7862A REP
[2]  
GRUBB RL, 1980, JUL PES SUMM M MINN
[3]   POWER TRANSFORMERS AND SHUNT REACTORS FOR ARCTIC REGIONS [J].
LAMPE, W .
IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (01) :217-224
[4]   LOW-TEMPERATURE PERFORMANCE OF NAPHTHENIC AND PARAFFINIC OILS IN TRANSFORMERS AND AUTOMATIC CIRCUIT RECLOSERS [J].
LANGHAME, Y ;
CASTONGUAY, J ;
BEDARD, N ;
STONGE, H .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1985, 104 (04) :910-917
[5]  
LANGHAME Y, 1977, IREQ1664 REP
[6]  
LANGHAME Y, 1980, IREQ2244 REP
[7]  
LANGHAME Y, 1983, STUDY THERMAL BEHAVI
[8]  
MONTSINGER VM, 1942, AIEE T, V61, P906
[9]  
MONTSINGER VM, 1951, TRANSFORMER ENG, P305
[10]  
MONTSINGER VM, 1942, AIEE T, V61, P993