INVESTIGATION OF THE EFFECTS OF THERMOSTATIC AND ELECTRONIC EXPANSION VALVES ON THE STEADY-STATE AND TRANSIENT PERFORMANCE OF COMMERCIAL CHILLERS

被引:13
作者
TASSOU, SA
ALNIZARI, HO
机构
[1] Department of Mechanical Engineering, Brunel, The University of West London, Uxbridge
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 1993年 / 16卷 / 01期
关键词
COMMERCIAL CHILLERS; EXPANSION VALVES; COP;
D O I
10.1016/0140-7007(93)90021-Y
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper investigates the steady-state performance and transient response of a commercial fixed-speed on-off controlled chiller and presents comparative performance results obtained during operation with a thermostatic and with an electronic expansion valve. The aim was to establish the effect of the two valves on the transient and steady-state performance of the chiller and to quantify the effects of on-off cycling losses during part-load operation. The results indicate that the chiller has a very fast response during start-up and that cycling losses are very low. The thermostatic expansion valve gives a slightly faster response than the electronic expansion valve with the penalty, however, of less stable operation with larger superheat oscillations at steady-state conditions.
引用
收藏
页码:49 / 56
页数:8
相关论文
共 8 条
[1]  
Chi J., 1982, INT J REFRIG, V5, P176, DOI DOI 10.1016/0140-7007(82)90099-8
[2]  
DANING P, 1963, J REFRIG, V6, P52
[3]  
HUELLE ZR, 1988, 12 INT REFR C MADR
[4]  
TASSOU SA, 1991, HEAT RECOVERY SYSTEM, V2, P541
[5]   SYSTEM MEAN VOID FRACTION MODEL FOR PREDICTING VARIOUS TRANSIENT PHENOMENA ASSOCIATED WITH 2-PHASE EVAPORATING AND CONDENSING FLOWS [J].
WEDEKIND, GL ;
BHATT, BL ;
BECK, BT .
INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 1978, 4 (01) :97-114
[6]  
WEDEKIND GL, 1977, ASHRAE J, V8, P74
[7]  
1988, ELECTRIC EXPANSION V
[8]  
1987, EPRI EM5082 RES REP