MEASURED AND PREDICTED COLD LOAD PICK-UP AND FEEDER PARAMETER DETERMINATION USING THE HARMONIC MODEL ALGORITHM

被引:6
作者
LAW, J
ELLIOTT, L
MINFORD, D
STORMS, M
机构
[1] ELLIOTT ELECT ENGN,MOSCOW,ID
[2] KOOTENAI ELECT COOPERAT,HAYDEN,ID
[3] BONNEVILLE POWER ADM,SPOKANE,WA
关键词
FEEDER; OUTAGE; RESTORATION; DIVERSITY; COLD LOAD PICKUP; STEP VOLTAGE TEST;
D O I
10.1109/59.476039
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents theory of the ''Cold Load Harmonic'', CLHARM, model algorithm for simulation of power feeder currents resulting from both Cold Load Pickup, CLPU, and the ''Step Voltage Test'', STEPV. The STEPV method is also presented. Feeder parameters obtained from field STEPV measurement are used to predict CLPU on that feeder using the CLHARM algorithm. STEPV test measurements and actual measured CLPU currents on the same feeder are compared with computer predictions. The CLHARM aggregates feeder thermostatically controlled load to simulate regain of diversity during outage restoration. All feeder weather sensitive load is lumped in CLHARM, using mean parameter values of thermodynamic model. The ultimate objective of this work is experimentally obtained feeder ''signatures'' for CLPU prediction as a feeder design tool.
引用
收藏
页码:1756 / 1764
页数:9
相关论文
共 7 条
[1]  
ATHOW D, 1987, THESIS U IDAHO
[2]  
ATHOW D, 1994, WIN IEEE PES M, V94
[3]  
AUDLIN LJ, 1949, ELECTRICAL WORLD SEP, P99
[4]  
HUNT M, 1987, THESIS U IDAHO DEP E
[5]  
PRICE WW, SPECIAL CONSIDERATIO
[6]  
TAYLOR CW, 1991, POWER SYSTEM DYNAMIC
[7]  
1963, REA B, V452