INACTIVATION OF LEGIONELLA-PNEUMOPHILA BY MONOCHLORAMINE

被引:22
作者
CUNLIFFE, DA
机构
[1] State Water Laboratory, Engineering and Water Supply Department, Salisbury, South Australia
来源
JOURNAL OF APPLIED BACTERIOLOGY | 1990年 / 68卷 / 05期
关键词
D O I
10.1111/j.1365-2672.1990.tb02896.x
中图分类号
Q81 [生物工程学(生物技术)]; Q93 [微生物学];
学科分类号
071005 ; 0836 ; 090102 ; 100705 ;
摘要
Chloramination which is used in South Australia to control the growth of Naegleria fowleri, was investigated to see if it would also control that of Legionella pneumophila. It was found that L. pneumophila was more sensitive than Escherichia coli to monochloramine. At 1.0 mg/l, a 99% kill of L. pneumophila was achieved in 15 min compared with 37 min for a 99% kill of E. coli. Combined with the stability of monochloramine, even at elevated temperatures, the results suggest that this disinfectant would control the growth of L. pneumophila in water distribution systems. Copyright © 1990, Wiley Blackwell. All rights reserved
引用
收藏
页码:453 / 459
页数:7
相关论文
共 28 条
[1]  
[Anonymous], 1985, STANDARD METHODS EXA, V16th, P306
[2]  
BAIRD IM, 1983, LEGIONELLA, P333
[3]  
BARRETT SE, 1985, J AM WATER WORKS ASS, V77, P50
[4]  
BARTLETZ CLR, 1983, LEGIONELLA, P210
[5]  
BEST M, 1983, LANCET, V2, P307
[7]   ROLE OF STAGNATION AND OBSTRUCTION OF WATER-FLOW IN ISOLATION OF LEGIONELLA-PNEUMOPHILA FROM HOSPITAL PLUMBING [J].
CIESIELSKI, CA ;
BLASER, MJ ;
WANG, WLL .
APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 1984, 48 (05) :984-987
[8]  
COLBOURNE JS, 1984, LANCET, V1, P210
[9]   LEGIONELLA AND PUBLIC WATER-SUPPLIES [J].
COLBOURNE, JS ;
DENNIS, PJ ;
TREW, RM ;
BERRY, C ;
VESEY, G .
WATER SCIENCE AND TECHNOLOGY, 1988, 20 (11-12) :5-10
[10]  
FISHERHOCH SP, 1982, LANCET, V1, P1073