VOLTAGE STABILITY CONDITION IN A POWER TRANSMISSION-SYSTEM CALCULATED BY SENSITIVITY METHODS

被引:112
作者
FLATABO, N [1 ]
OGNEDAL, R [1 ]
CARLSEN, T [1 ]
机构
[1] NORWEGIAN STATE POWER BOARD,OSLO,NORWAY
关键词
D O I
10.1109/59.99379
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A new method for determination of voltage stability condition in a power system is presented. The method is based on sensitivity techniques, taking into account the limits on reactive power generation capacities. A distance to voltage collapse in terms of MVAr is defined as a measure of system security. Results from calculations on a 480-bus network with 140 generators is presented. The method can be efficiently used for reactive power security evaluation both in system planning and operation. © 1990 IEEE