CHARGE COMPARISON PROTECTION OF TRANSMISSION-LINES - RELAYING CONCEPTS

被引:10
作者
ERNST, LJ [1 ]
HINMAN, WL [1 ]
QUAM, DH [1 ]
THORP, JS [1 ]
机构
[1] CORNELL UNIV,ITHACA,NY 14853
关键词
CHARGE COMPARISON; CURRENT DIFFERENTIAL RELAYING; TRANSMISSION LINE PROTECTION; DIGITAL RELAYING;
D O I
10.1109/61.156986
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Charge comparison is a new transmission line protection system. It is a form of current differential relaying. Charge comparison largely resolves the traditional problems of current differential relaying of transmission lines: protection is lost if channel fails, large channel capacity required and precise channel delay compensation required. This new technique is suitable for the protection of two - or three-terminal ac transmission lines, of all lengths and voltage levels, with or without series or shunt compensation, with three-pole or single-pole tripping.
引用
收藏
页码:1834 / 1852
页数:19
相关论文
共 20 条
[1]   MICROPROCESSOR BASED DIGITAL RELAYS APPLICATION IN TEPCO [J].
AKIMOTO, Y ;
MATSUDA, T ;
MATSUZAWA, K ;
YAMAURA, M ;
KONDOW, R ;
MATSUSHIMA, T .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (05) :2390-2398
[2]  
ALBRECHT NP, 1992, JAN IEEE PES WINT M
[3]  
ALEXANDER GE, 1991, APR TEX AM REL C
[4]  
ANDERSSON F, 1990, OCT W PROT REL C
[5]  
BARNES HC, 1955, AIEE T, V74, P417
[6]  
ELMORE WA, 1989, MAY GEORG TECH PROT
[7]  
HOFFMAN GR, 1990, Patent No. 4939617
[8]  
LEFRANCOIS MJ, 1978, OCT W PROT REL C
[9]  
NORMAN P, IEEE92WM2105PWRD
[10]   IMPROVED PHASE-COMPARISON RELAYING WITH HIGHER PERFORMANCE [J].
OKAMURA, M ;
ANDOW, F ;
SUZUKI, S .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (02) :522-527