SUPPRESSION OF STATIC ELECTRIFICATION OF INSULATING OIL FOR LARGE POWER TRANSFORMERS

被引:44
作者
IEDA, M
OKUGO, H
TSUKIOKA, H
GOTO, K
MIYAMOTO, T
KOHNO, Y
机构
[1] TOSHIBA CORP,KAWASAKI 210,JAPAN
[2] HITACHI LTD,HITACHI,IBARAKI 316,JAPAN
[3] TOKYO ELECT POWER CO INC,TOKYO,JAPAN
[4] MITSUBISHI ELECT CORP,AKO,JAPAN
[5] NIPPON OIL CO,YOKOHAMA,JAPAN
来源
IEEE TRANSACTIONS ON ELECTRICAL INSULATION | 1988年 / 23卷 / 01期
关键词
ELECTRIC TRANSFORMERS - Oil Filled - ELECTROSTATICS - Electric Charge;
D O I
10.1109/14.2349
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The results of various studies on insulating-oil characteristics performed in Japan are summarized. The development of a charge-measuring apparatus and method of suppressing charging tendency by BTA (benzotriazol) additive are discussed. Field data obtained on a transformer over three years indicate long-term reliability.