DESICCANT DEGRADATION IN DESICCANT COOLING SYSTEMS - AN EXPERIMENTAL-STUDY

被引:3
作者
PESARAN, AA
机构
[1] National Renewable Energy Laboratory, Golden, CO, 80401
来源
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME | 1993年 / 115卷 / 04期
关键词
D O I
10.1115/1.2930052
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
We conducted experiments to quantify the effects of thermal cycling and exposure to contamination on solid desiccant materials that may be used in desiccant cooling systems. The source of contamination was cigarette smoke, which is considered one of the worst pollutants in building cooling applications. We exposed five different solid desiccants to ''ambient'' and ''contaminated'' humid air: silica gel, activated alumina, activated carbon, molecular sieves, and lithium chloride. We obtained the moisture capacity of samples as a function of exposure time. Compared to virgin desiccant samples, the capacity loss caused by thermal cycling with humid ambient air was 10 percent to 30 percent for all desiccants. The capacity loss because of combined effect of thermal cycling with ''smoke-filled'' humid air was between 30 percent to 70 percent. The higher losses occurred after four months of experiment time, which is equivalent to four to eight years of field operation. Using a system model and smoke degradation data on silica gel, we predicted that, for low-temperature regeneration, the loss in performance of a ventilation-cycle desiccant cooling system would be between 10 percent to 35 percent, in about eight years, with higher value under worst conditions.
引用
收藏
页码:212 / 219
页数:8
相关论文
共 10 条
[1]  
CZANDERNA AW, 1984, SERITR2552217 SOL EN
[2]  
HINES AL, 1990, GRI900194 GAS RES I
[3]  
Meyer B., 1983, INDOOR AIR QUALITY
[4]  
MOSEMAN MH, 1982, CHEM ENG PROG, V78, P78
[5]  
PESARAN AA, 1993, ASME, V15, P237
[6]  
PESARAN AA, 1989, 1989 P ASME SOL EN D, P449
[7]  
PESARAN AA, 1991, ASHRAE T 1, V96, P595
[8]  
PESARAN AA, 1990, SERITP2543677 SOL EN
[9]  
PESARAN AA, 1991, NRELPR2543457 NAT RE
[10]  
WADDEN A, 1983, INDOOR AIR POLLUTION