A NEW APPROACH TO DETERMINE TRANSIENT GENERATOR WINDING AND DAMPER CURRENTS IN CASE OF INTERNAL AND EXTERNAL FAULTS AND ABNORMAL OPERATION

被引:27
作者
KULIG, TS
BUCKLEY, GW
LAMBRECHT, D
LIESE, M
机构
[1] SIEMANS AG,KRAFTWERK,UNION AG,DEPT DEV & ELECT DESIGN TURBINE GENERATORS,MULHEIM,GERMANY
[2] GEC LTD,LONDON,ENGLAND
[3] SIEMANS AG,KRAFWERK UNION AG,DEPT GENERATOR DEV,MULHEIM,GERMANY
关键词
D O I
10.1109/60.50815
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper forms the third in a three-part series describing the theory and application of a new method for analyzing the steady-state and tranSient currents In the stator, rotor and damper windings of a large generator It describes the application of the theoretical method to five classes of problems of practical importance. These are the classic cases of 180 degree out-of-phase synchronization, a three-phase symmetrical short circuit, clearing of a three-phase system fault. internal fault and 6% unbalanced steady-state negative sequence load The paper shows the individual damper bar current and energy or electric power loadings for these cases and, for one example, the time variations of stator and damper winding currents. © 1990 IEEE
引用
收藏
页码:70 / 78
页数:9
相关论文
共 5 条
[1]  
BARRETT P, 1970, STRESS TURBOGENERATO
[2]  
COULSON MA, 1980, TRANSIENT NEGATIVE S
[3]  
KULIG TS, 1986, WIN IEEE M NEW ORL
[4]   METHODS OF CALCULATION OF EDDY CURRENTS IN SOLID IRON [J].
LIESE, M .
ARCHIV FUR ELEKTROTECHNIK, 1977, 59 (02) :75-85
[5]  
NEITHOEFER GJ, 1975, IEEE T PAS, V94