NEW APPROACH TO POWER-LINE PROTECTION BASED UPON THE DETECTION OF FAULT INDUCED HIGH-FREQUENCY SIGNALS

被引:5
作者
JOHNS, AT
AGRAWAL, P
机构
关键词
D O I
10.1049/ip-c.1990.0041
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper outlines the salient features of a protection technique for transmission lines which utilises the high frequency components of fault generated noise. The approach is based on the non-unit type scheme, which makes use of a stack-tuner circuit connected to the coupling capacitor of a capacitor voltage transformer. The stack-tuner is tuned to a certain frequency bandwidth and is arranged to act as a high frequency switch. The signals derived from the stack-tuner are used to determe whether the fault is inside or outside the protected zone.
引用
收藏
页码:307 / 313
页数:7
相关论文
共 15 条
[1]   DETECTION OF DISTRIBUTION HIGH IMPEDANCE FAULTS USING BURST NOISE SIGNALS NEAR 60 HZ [J].
AUCOIN, M ;
RUSSELL, BD .
IEEE TRANSACTIONS ON POWER DELIVERY, 1987, 2 (02) :342-348
[2]   ULTRA HIGH-SPEED RELAY FOR EHV-UHV TRANSMISSION-LINES - DEVELOPMENT, DESIGN AND APPLICATION [J].
CHAMIA, M ;
LIBERMAN, S .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1978, 97 (06) :2104-2116
[3]  
CORNICK KJ, 1989, IEE P C, V12, P18
[4]  
DOMMEL HW, 1978, JAN IEEE PES WIN M N
[5]   PERFORMANCE OF DISTANCE PROTECTION OF EHV FEEDERS UTILIZING SHUNT-REACTOR ARRANGEMENTS FOR ARC SUPPRESSION AND VOLTAGE CONTROL [J].
JOHNS, AT ;
ELNOUR, M ;
AGGARWAL, RK .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1980, 127 (05) :304-316
[6]   DIGITAL-SIMULATION OF FAULTED EHV TRANSMISSION-LINES WITH PARTICULAR REFERENCE TO VERY-HIGH-SPEED PROTECTION [J].
JOHNS, AT ;
AGGARWAL, RK .
PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1976, 123 (04) :353-359
[7]   DIGITAL-SIMULATION OF EHV SYSTEMS UNDER SECONDARY ARCING CONDITIONS ASSOCIATED WITH SINGLE-POLE AUTORECLOSURE [J].
JOHNS, AT ;
ALRAWI, AM .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1982, 129 (02) :49-58
[8]  
JOHNS AT, 1986, BTGATJ1 BRIT TECHN G
[9]  
MEHDI AM, 1984, THESIS U BATH
[10]   BEHAVIOR OF LOW-FREQUENCY SPECTRA DURING ARCING FAULT AND SWITCHING EVENTS [J].
RUSSELL, BD ;
CHINCHALI, RP ;
KIM, CJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :1485-1492