STUDY OF A CIRCUIT-BREAKER ARC WITH SELF-GENERATED FLOW .3. THE POST-ARC PHASE

被引:24
作者
GLEIZES, A [1 ]
MITICHE, M [1 ]
VANDOAN, P [1 ]
机构
[1] ALSTHOM,GEC,F-69611 VILLEURBANNE,FRANCE
关键词
D O I
10.1109/27.62361
中图分类号
O35 [流体力学]; O53 [等离子体物理学];
学科分类号
070204 ; 080103 ; 080704 ;
摘要
The third part of this study of a circuit-breaker arc with self-generated flow concerns the model of the post-arc phase. The greater interruption capability of SF6 compared to N2, already suggested in Part II [2], is confirmed by the following results: Amplitude and duration of the post-arc current are much lower in SF6; and the maximum value of the rate of rise of recovery voltage (RRRV) is about three times higher in SF6 than in N2. The model also predicts the existence of a plateau in post-arc current variation and the original behavior of this type of circuit-breaker: Interrupting efficiency increases with the current peak in the initial phase.
引用
收藏
页码:12 / 19
页数:8
相关论文
共 26 条
[1]   POST-ARC CURRENT IN HIGH-VOLTAGE SF6 CIRCUIT-BREAKERS WHEN BREAKING AT UP TO 63 KA [J].
BLEZ, B ;
GUILLOUX, C .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (02) :1056-1062
[2]   DIELECTRIC RECOVERY OF AN AXIALLY BLOWN SF6-ARC AFTER CURRENT ZERO .3. COMPARISON OF EXPERIMENT AND THEORY [J].
BRAND, KP ;
EGLI, W ;
NIEMEYER, L ;
RAGALLER, K ;
SCHADE, E .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 1982, 10 (03) :162-172
[3]   STUDY OF A CIRCUIT-BREAKER ARC WITH SELF-GENERATED FLOW .2. THE FLOW PHASE [J].
GLEIZES, A ;
RAHAL, AM ;
PAPADOPOULOS, S ;
VACQUIE, S .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 1988, 16 (06) :615-622
[4]   CALCULATION OF THERMODYNAMIC PROPERTIES AND TRANSPORT-COEFFICIENTS FOR SF6-N-2 MIXTURES IN THE TEMPERATURE-RANGE 1,000-30,000-K [J].
GLEIZES, A ;
RAZAFINIMANANA, M ;
VACQUIE, S .
PLASMA CHEMISTRY AND PLASMA PROCESSING, 1986, 6 (01) :65-78
[5]   STUDY OF A CIRCUIT-BREAKER ARC WITH SELF-GENERATED FLOW .1. ENERGY-TRANSFER IN THE HIGH-CURRENT PHASE [J].
GLEIZES, A ;
RAHAL, AM ;
DELACROIX, H ;
VANDOAN, P .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 1988, 16 (06) :606-614
[6]   THEORETICAL DESCRIPTION OF CURRENT INTERRUPTION IN HV GAS BLAST BREAKERS [J].
HERMANN, W ;
RAGALLER, K .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1977, 96 (05) :1546-1555
[7]   INVESTIGATION ON PHYSICAL PHENOMENA AROUND CURRENT ZERO IN HV GAS BLAST BREAKERS [J].
HERMANN, W ;
KOGELSCHATZ, U ;
NIEMEYER, L ;
RAGALLER, K ;
SCHADE, E .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1976, 95 (04) :1165-1176
[8]  
KRENEK P, 1983, ACTA TECH CSAV, P549
[9]  
KRENEK P, 1978, ACTA TECHNICA CSAV, P339
[10]  
Lee H., 1982, Seventh International Conference on Gas Discharges and their Applications, P13