ANALYSIS OF HIGH-IMPEDANCE FAULT GENERATED SIGNALS USING A KALMAN FILTERING APPROACH

被引:110
作者
GIRGIS, AA
CHANG, WB
MAKRAM, EB
机构
[1] Clemson University, Department of Electrical and Computer Engineering, Clemson, South Carolina
关键词
Harmonic Analysis; High-Impedance Faults. Signal Processing; Kalman Filtering;
D O I
10.1109/61.103666
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
High-impedance faults are accompanied by variations in the 60-Hz and harmonic components. However, these variations are not stationary, but time-varying in nature due to the dynamics of the fault arc. Therefore, an approach that accounts for the time-varying nature of the fundamental and harmonic components is developed. This approach is based on Kalman filtering theory to obtain the best estimation of the time variations of the fundamental and harmonic components. Four actual recorded data sets for staged arcing fault on different types of soil are investigated by the proposed Kalman filtering technique. The time variations of fundamental and low-order harmonic components significantly contribute to high-impedance fault detection using the features presented in this paper. © 1990 IEEE