PERFORMANCE OF INSULATORS COVERED WITH SNOW OR ICE

被引:79
作者
FUJIMURA, T
NAITO, K
HASEGAWA, Y
机构
[1] NGK INSULATORS, LTD., Nagoya
来源
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS | 1979年 / 98卷 / 05期
关键词
D O I
10.1109/TPAS.1979.319479
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes the results of investigation made into the performance of insulators covered with snow or ice. The AC and DC withstand voltages of snow-covered insulators were characterized by the conductivity of water melted from the snow. The AC withstand voltage of ice-coated insulators was characterized by the length of icicles and conductivity of the water melted from the ice. And the switching impulse flashover voltage of snow-covered insulator strings was almost proportional to gap length between the arcing horns or the insulator strings. Flashover voltage of a 75% snow-covered insulator string, which means the worst case, was 40–65% of the positive wet flashover voltage of the clean insulator string. Copyright © 1979 by The Institute of Electrical and Electronics Engineers. Inc.
引用
收藏
页码:1621 / 1631
页数:11
相关论文
共 13 条
[1]  
ELY GHA, 1978, IEEE T PAS, V97, P2187
[2]  
Hara M., 1978, Canadian Electrical Engineering Journal, V3, P15
[3]  
HARA M, 1978, F786777 IEEE PAP
[4]  
HIROSE Y, 1972, CIGRE3302 PAP
[5]   AC FLASHOVER TESTS AT PROJECT UHV ON ICE-COATED INSULATORS [J].
KAWAI, M .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1970, PA89 (08) :1800-&
[6]   PERFORMANCE OF LINE INSULATORS UNDER RIME ICE [J].
KHALIFA, MM ;
MORRIS, RM .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1967, PA86 (06) :692-&
[7]  
LEE LY, 1975, SUM IEEE PES M
[8]  
PHAN CL, 1977, CANADIAN ELECT ENG J, V2, P24
[9]   EFFECTS OF ICING ON DC INSULATION STRENGTH [J].
RENNER, PE ;
HILL, HL ;
RATZ, O .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1971, PA90 (03) :1201-&
[10]  