THE EFFICACY OF CHLORINATION AND FILTRATION IN THE CONTROL AND ERADICATION OF LEGIONELLA FROM DENTAL CHAIR WATER-SYSTEMS

被引:44
作者
PANKHURST, CL
PHILPOTTHOWARD, JN
HEWITT, JH
CASEWELL, MW
机构
[1] KINGS COLL, SCH MED & DENT, DEPT MED MICROBIOL, LONDON SE5 9RX, ENGLAND
[2] DULWICH HOSP, PUBL HLTH LAB, LONDON SE22, ENGLAND
关键词
chlorination; control measures for Legionella spp; dental water quality; Legionella pneumophila;
D O I
10.1016/0195-6701(90)90044-O
中图分类号
R1 [预防医学、卫生学];
学科分类号
1004 ; 120402 ;
摘要
The apparent failure of hyperchlorination and continuous dosing with chlorine to eliminate Legionellae from a dental teaching hospital water supply prompted a prospective study to evaluate charcoal filters as a means of decontamination. Legionella pneumophila serogroup 10 and L. bozemanii serogroup 2 were isolated from dental units yielding 101-103 colony forming units (cfu) ml-1 with total bacterial counts in the range 102-> 104 cfu ml-1. After chair-side installation of charcoal filters bacterial contamination of the dental unit water was prevented and Legionellae were initially not detected, but after 7 days the total count returned to pre-filtration levels of >104 cfu ml-1; L. pneumophila serogroup 10 was eliminated but L. bozemanii serogroup 2 persisted. These results suggest that neither chlorination nor charcoal filtration deal adequately with the potential hazard of Legionella spp. in dental water. © 1990.
引用
收藏
页码:9 / 18
页数:10
相关论文
共 28 条
[1]  
BARTLETT CLR, 1986, LEGIONELLA INFECTION
[2]   NEW SEROGROUP OF LEGIONELLA-PNEUMOPHILA, SEROGROUP-8 [J].
BISSETT, ML ;
LEE, JO ;
LINDQUIST, DS .
JOURNAL OF CLINICAL MICROBIOLOGY, 1983, 17 (05) :887-891
[3]   AEROSOLS CONTAINING LEGIONELLA-PNEUMOPHILA GENERATED BY SHOWER HEADS AND HOT-WATER FAUCETS [J].
BOLLIN, GE ;
PLOUFFE, JF ;
PARA, MF ;
HACKMAN, B .
APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 1985, 50 (05) :1128-1131
[4]   ROLE OF STAGNATION AND OBSTRUCTION OF WATER-FLOW IN ISOLATION OF LEGIONELLA-PNEUMOPHILA FROM HOSPITAL PLUMBING [J].
CIESIELSKI, CA ;
BLASER, MJ ;
WANG, WLL .
APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 1984, 48 (05) :984-987
[5]  
COLBOURNE JS, 1986, ISRAEL J MED SCI, V22, P633
[6]   CONTROL OF LEGIONELLA IN HOSPITALS [J].
EDELSTEIN, PH .
JOURNAL OF HOSPITAL INFECTION, 1986, 8 (02) :109-115
[7]   IMPROVED SEMISELECTIVE MEDIUM FOR ISOLATION OF LEGIONELLA-PNEUMOPHILA FROM CONTAMINATED CLINICAL AND ENVIRONMENTAL SPECIMENS [J].
EDELSTEIN, PH .
JOURNAL OF CLINICAL MICROBIOLOGY, 1981, 14 (03) :298-303
[8]   NOSOCOMIAL LEGIONNAIRES-DISEASE - A GLOBAL PERSPECTIVE [J].
EDELSTEIN, PH .
JOURNAL OF HOSPITAL INFECTION, 1988, 11 :182-188
[9]   THE SOURCE, FREQUENCY AND EXTENT OF BACTERIAL-CONTAMINATION OF DENTAL UNIT WATER-SYSTEMS [J].
FITZGIBBON, EJ ;
BARTZOKAS, CA ;
MARTIN, MV ;
GIBSON, MF ;
GRAHAM, R .
BRITISH DENTAL JOURNAL, 1984, 157 (03) :98-101
[10]   PREVALENCE OF LEGIONELLA-SPECIFIC IGG AND IGM ANTIBODY IN A DENTAL CLINIC POPULATION [J].
FOTOS, PG ;
WESTFALL, HN ;
SNYDER, IS ;
MILLER, RW ;
MUTCHLER, BM .
JOURNAL OF DENTAL RESEARCH, 1985, 64 (12) :1382-1385