ROLE OF AIR SAMPLING IN INVESTIGATION OF AN OUTBREAK OF LEGIONNAIRES-DISEASE ASSOCIATED WITH EXPOSURE TO AEROSOLS FROM AN EVAPORATIVE CONDENSER

被引:70
作者
BREIMAN, RF [1 ]
COZEN, W [1 ]
FIELDS, BS [1 ]
MASTRO, TD [1 ]
CARR, SJ [1 ]
SPIKA, JS [1 ]
MASCOLA, L [1 ]
机构
[1] LOS ANGELES CTY DEPT HLTH SERV,DIV ACUTE COMMUNICABLE DIS,LOS ANGELES,CA
关键词
D O I
10.1093/infdis/161.6.1257
中图分类号
R392 [医学免疫学]; Q939.91 [免疫学];
学科分类号
100102 ;
摘要
Epidemiologic studies have suggested that legionnaires' disease can betransmitted to susceptible hosts by contaminated aerosolized water from cooling towers and evaporative condensers; however, epidemic strains of Legionella have not been isolated by air sampling at such sites during epidemiologic investigations. An outbreak of legionnaires' disease occurred at a retirement hotel; Legionella pneumophila serogroup 1 was isolated from an evaporative condenser and from potable water. A case-control study showed that the only significant exposure risk was in area A. L. pneumophila serogroup 1 was isolated during air sampling near the evaporative condenser exhaust site, the air conditioning intake vent, and an air vent in area A, but not in shower stalls. Monoclonal antibody subtype patterns of L. pneumophila serogroup 1 isolates from patients matched those from the evaporative condenser but not from shower water. Air sampling and monoclonal antibody subtyping results support epidemiologic evidence that the evaporative condenser was the source of this outbreak. © 1990, University of Chicago. All rights reserved.
引用
收藏
页码:1257 / 1261
页数:5
相关论文
共 32 条
  • [1] NEW SAMPLER FOR THE COLLECTION, SIZING, AND ENUMERATION OF VIABLE AIRBORNE PARTICLES
    ANDERSEN, AA
    [J]. JOURNAL OF BACTERIOLOGY, 1958, 76 (05) : 471 - 484
  • [2] NOSOCOMIAL LEGIONNAIRES-DISEASE CAUSED BY AEROSOLIZED TAP WATER FROM RESPIRATORY DEVICES
    ARNOW, PM
    CHOU, T
    WEIL, D
    SHAPIRO, EN
    KRETZSCHMAR, C
    [J]. JOURNAL OF INFECTIOUS DISEASES, 1982, 146 (04) : 460 - 467
  • [3] DETECTION AND RECOVERY OF LEGIONELLA IN WATER
    BARBAREE, JM
    MORRILL, WE
    FIELDS, BS
    MARTIN, WT
    SANDEN, GN
    [J]. TOXICITY ASSESSMENT, 1988, 3 (05): : 479 - 490
  • [4] BARBAREE JM, 1987, C LEGIONELLA FACULE, P51
  • [5] AEROSOLS CONTAINING LEGIONELLA-PNEUMOPHILA GENERATED BY SHOWER HEADS AND HOT-WATER FAUCETS
    BOLLIN, GE
    PLOUFFE, JF
    PARA, MF
    HACKMAN, B
    [J]. APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 1985, 50 (05) : 1128 - 1131
  • [6] BREIMAN RF, 1990, IN PRESS JAMA
  • [7] Breslow NE, 1980, IARC SCI PUBLICATION, V1
  • [8] BROWN JH, 1950, AM J PUBLIC HEALTH, V40, P450
  • [9] CHERRY WB, 1978, J CLIN MICROBIOL, V8, P329
  • [10] LEGIONNAIRES-DISEASE OUTBREAK AT AN ATLANTA, GEORGIA, COUNTRY CLUB - EVIDENCE FOR SPREAD FROM AN EVAPORATIVE CONDENSER
    CORDES, LG
    FRASER, DW
    SKALIY, P
    PERLINO, CA
    ELSEA, WR
    MALLISON, GF
    HAYES, PS
    [J]. AMERICAN JOURNAL OF EPIDEMIOLOGY, 1980, 111 (04) : 425 - 431