ANALYSIS OF A 3-DIMENSIONAL VENTILATION FLOW - EXPERIMENTAL VALIDATION ON A WATER SCALE-MODEL OF NUMERICAL SIMULATIONS

被引:8
作者
FONTAINE, JR
BIOLLEY, F
RAPP, R
SERIEYS, JC
CUNIN, JC
机构
[1] Institut National de Recherche et de Sécurité, Vandoeuvre Cédex, 54501, Avenue de Bourgogne
关键词
D O I
10.1080/10407789408956002
中图分类号
O414.1 [热力学];
学科分类号
摘要
Laboratory and numerical experiments were conducted in order to study the flow within an isothermal parallelepipedic test room. The air is injected through a complex diffuser (made of 84 nozzles) near the ceiling and is evacuated through a rectangular exist just below the inlet. Measurements were performed on a hydraulic model at 1/6 scale. The parameters were determined according to a Reynolds similitude. Both laser Doppler anemometry and flow visualization were used. Numerical simulations were carried out using the EOL-3D software developed at the Institute National de Recherche et de Securite. A comparison between experimental results and numerical predictions is presented.
引用
收藏
页码:431 / 451
页数:21
相关论文
共 17 条
[1]  
BERLANDIE P, 1989, 10TH AIVC C ESP
[2]  
DEMUREN AO, 1987, COMPUTER PROGRAM SOL
[3]  
FONTAINE JR, 1991, 3RD INT S VENT CONT
[4]  
GOSMAN AD, 1980, ASME J FLUIDS ENG, V102, P316
[5]  
GOSMAN AD, 1976, GENERAL COMPUTER PRO
[6]  
HEIKKINEN J, 1989, AN201SF91VTT08 TECHN
[7]   CALCULATION OF LOW-REYNOLDS-NUMBER PHENOMENA WITH A 2-EQUATION MODEL OF TURBULENCE [J].
JONES, WP ;
LAUNDER, BE .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1973, 16 (06) :1119-1130
[8]  
Launder B. E., 1974, Computer Methods in Applied Mechanics and Engineering, V3, P269, DOI 10.1016/0045-7825(74)90029-2
[9]  
LEMAIRE AD, 1990, TNO AN201NL90TNOTPD0
[10]  
LEMAIRE AD, 1992, ROOM AIR CONTAMINANT