GROUNDING SYSTEM TESTS FOR ANALYSIS OF FAULT-INDUCED VOLTAGES ON COMMUNICATION CABLES

被引:10
作者
DICK, EP
ERVEN, CC
HARVEY, SM
机构
[1] Ontario Hydro, Toronto
来源
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS | 1979年 / 98卷 / 06期
关键词
D O I
10.1109/TPAS.1979.319411
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
To avoid failures of communication lines serving electric power stations during line-to-ground faults, an analysis of the expected voltages must be carried out for each projected station. A method for predicting reliable results without conducting staged-fault tests is described. The technique uses ac current injection at 5 to 10 Hz away from the power-system frequency to simulate a fault condition, and a sensitive detection scheme for measuring the amplitude and phase of secondary voltages and currents in the presence of power-system interference. The method is employed to predict voltage stresses on communication cables in a large multi-station power-system complex. © 1979 IEEE
引用
收藏
页码:2115 / 2125
页数:11
相关论文
共 10 条
[1]  
ATYEO GL, 1977 TOR JOINT C SC3
[2]  
DAWALIBI F, 1979, SUM IEEE PES M VANC
[3]  
DAWALIBI F, 1977, SUM IEEE M MEX
[4]  
GROVER FW, 1946, INDUCTANCE CALCULATI, P33
[5]  
KUUSSAARI M, 1978, P CIGRE SESSION
[6]  
KUUSSAARI M, 1978, CIGRE3602 PAP
[7]  
SELJESETH H, 1977 TOR JOINT C SC3
[8]  
1976, IEEE T PAS, V95, P1216
[9]  
1977, IEEE T PAS, V96, P1256
[10]  
1976, STD80 IEEE