CPFLOW - A PRACTICAL TOOL FOR TRACING POWER-SYSTEM STEADY-STATE STATIONARY BEHAVIOR DUE TO LOAD AND GENERATION VARIATIONS

被引:458
作者
CHIANG, HD
FLUECK, AJ
SHAH, KS
BALU, N
机构
[1] UNION ELECT CO,DEPT SYST PLANNING,ST LOUIS,MO 63166
[2] ELECT POWER RES INST,DIV ELECT SYST,POWER SYST PLANNING & OPERAT,PALO ALTO,CA 94303
关键词
D O I
10.1109/59.387897
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
In this paper, a computer package called CPFLOW which is a comprehensive tool for tracing power system steady-state stationary behavior due to parameter variations is presented. Tire variations include general bus real and/or reactive loads, area real and/or reactive loads, or system-wide real and/or reactive loads, and real generation at P-V buses (e.g. determined ly economic dispatch or participation factor). The main advantages of CPFLOW over repetitive power flow calculations are its computational speed and reliability as well as its wide applicability. A detailed description of the implementation regarding the predictor, corrector, step-size control and parameterizations employed in CPFLOW is presented. CPFLOW has comprehensive modeling capability and can handle power systems up to 12000 buses. For an illustrative purpose, CPFLOW is applied to a 3500-bus power system with a comprehensive set of operational limits and controls.
引用
收藏
页码:623 / 630
页数:8
相关论文
共 10 条
[1]
THE CONTINUATION POWER FLOW - A TOOL FOR STEADY-STATE VOLTAGE STABILITY ANALYSIS [J].
AJJARAPU, V ;
CHRISTY, C .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (01) :416-423
[2]
POINT OF COLLAPSE AND CONTINUATION METHODS FOR LARGE AC DC SYSTEMS [J].
CANIZARES, CA ;
ALVARADO, FL .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (01) :1-8
[3]
CHIANG HD, 1990, 10TH P POW SYST COMP
[4]
THE CONTINUATION METHOD IN POWER-SYSTEM OPTIMIZATION - APPLICATIONS TO ECONOMY-SECURITY FUNCTIONS [J].
HUNEAULT, M ;
FAHMIDEHVOJDANI, A ;
JUMAN, M ;
CALDERON, R ;
GALIANA, FD .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1985, 104 (01) :114-124
[5]
AN INVESTIGATION OF THE SOLUTION TO THE OPTIMAL POWER FLOW PROBLEM INCORPORATING CONTINUATION METHODS [J].
HUNEAULT, M ;
GALIANA, FD .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1990, 5 (01) :103-110
[6]
HUNEAULT M, 1990, IEEE T POWER SYSTEMS, V5, P416
[7]
CALCULATION OF CRITICAL LOADING CONDITION WITH NOSE CURVE USING HOMOTOPY CONTINUATION METHOD [J].
IBA, K ;
SUZUKI, H ;
EGAWA, M ;
WATANABE, T .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1991, 6 (02) :584-593
[8]
KUBICEK M, 1983, SPRINGER SERIES COMP
[9]
SEYDEL R, 1988, EQUILIBRIUM CHOAS PR
[10]
1992, EPRI FINAL REPORT IN