With the introduction of distributed generators (DG), the traditional distribution system characterized by radical network becomes a multi-source one. Therefore the accuracy of the equivalent model of distributed generators directly affects the precision of fault location. To solve this problem, this paper proposed a fault location method based on complex correlation Thevenin equivalent and strong tracking filter (STF) in distribution network with DG. Strong tracking filter (STF) can be used for real-time extraction of fundamental wave phase and amplitude of single phase voltage and current, and fast track the power parameters mutation. The method of complex correlation Thevenin equivalent takes into account the randomness of measurement data, DG impedance and load to overcome measurement error caused by the uncertainty of the data, so that the construction of the DG impedance model is more accurate. Simulation results show that the method of fault location proposed in this paper has advantages of high accuracy and strong robustness. © 2014 IFSA Publishing, S. L.