电压响应方法在电力变压器状态评估中的应用(英文)

被引:10
作者
张涛 [1 ]
蔡金锭 [1 ]
张孔林 [2 ]
机构
[1] College of Electrical Engineering and Automation,Fuzhou University
[2] Fujian Electric Power Testing & Research
关键词
voltage response; insulation aging; condition assess; power transformer; initial slope; return voltage; fault diagnosis; power equipment; moisture content; RVM; dielectric response;
D O I
10.13336/j.1003-6520.hve.2008.12.004
中图分类号
TM41 [电力变压器];
学科分类号
摘要
Power transformer is one of the most important equipment in the power system.Its operating condition affects the reliability of power supply directly.Therefore,in order to guarantee transformer operation safely and reliably,it is necessary to assess condition of power transformer accurately.Return voltage method based on voltage response measurements is still a new non-intrusive diagnosis method for internal insulation aging of transformer.In this paper the technique and application of return voltage measurement and some results of voltage response measurements of several transformers was introduced.Voltage response measurements were performed on various transformers with different voltage grades,various operating periods,different moisture contents and aging degrees on site.Derived moisture contents from return voltage measurement were compared with the corresponding moisture contents obtained from the analysis of oil samples.Based on on-site experiments and theoretical analysis,the criteria for insulation state of transformer are proposed.Moisture condition of transformer insulation can be determined by using return dominant time constant,and a good correlation between aging degree and the return voltage initial slopes of the aged transformers.Field test performed on several transformers,its interpretation of results are also presented,which proves that return voltage measurements can be used as a reliable tool for evaluating moisture content in transformer insulation.
引用
收藏
页码:2674 / 2680
页数:7
相关论文
共 15 条
[1]  
Dielectric response of oil-paper insulation systems of large moisture and temperature in homogeneity. Jaroslaw Gielniak,Marek Ossowski. Proceedings of the XI Vth International Symposiumon High Voltage Engineering . 2005
[2]  
Reviewof modern diagnostic techniques for assessinginsulation conditionin aged transformers. SAHA TAPAN K. IEEE Transactions on Dielectrics and Electrical Insulation . 2003
[3]  
Dielectric spectroscopy in time and frequency domain for HV power equipment I.Theoretical considerations. Zaengl W S. IEEE Electrical Insulation Magazine . 2003
[4]  
Dielectric Relaxation in Solids. Jonscher A K. . 1983
[5]  
Practical foundations of the RVM(return voltage method for oil/paper insulation diag-nosis). Csepes G,Hamos I,Brooks R,et al. 1998Annual Report Conference on Electrical In-sulation and Dielectric Phenomena . 1998
[6]  
Transformer insulation diagnosis:return voltage measurement and DCabsorption test. Paithankar A A,Pinto C T. Proc Electrical Insulation Conference and Electrical Manufacturing&Coil Winding Conf . 2001
[7]  
Impact of the condition of oil on the po-larization based diagnostics for assessing the condition of trans-formers insulation. Saha T K,Purkait P. IEEE Power Engineering Society Gen-eral Meeting . 2005
[8]  
Polarization spectrumanalysis for diagnosis of oil/paper insulation systems. Osvath P,Zahn H. Conference Record of the1994IEEE International Symposium on Electrical Insulation . 1994
[9]  
Ageing and mois-ture analysis of power transformer insulation systems. Leibfried T,Kachler AJ,Zaengl WS,et al. Proceedings of CIGRE Session2002 . 2002
[10]  
Development of a com-puter-based data logger for return voltage measurements. Lu Y H,Tan C K,Phung B T,et al. Proceedings of2002Australasian Universities Power Engineer-ing Conference:Part4(High Voltage,Condition Monito-ring) . 2002