共 24 条
±1100kV特高压直流换流站过电压与绝缘配合(英文)
被引:7
作者:
周浩
[1
]
邓旭
[1
]
王东举
[1
]
沈扬
[2
]
陈锡磊
[3
]
孙可
[4
]
机构:
[1] College of Electrical Engineering,Zhejiang University
[2] Zhejiang Electric Power Design Institute
[3] Zhejiang Cixi Power Supply Bureau
[4] Zhejiang Electric Power Company
来源:
关键词:
UHVDC power transmission;
±1;
100;
kV;
converter station;
arrester;
overvoltage protection;
insulation coordination;
insulation level;
D O I:
暂无
中图分类号:
TM86 [过电压及其防护];
TM853 [绝缘配合];
学科分类号:
080803 ;
摘要:
In order to specify the overvoltage and insulation level of equipments in ±1 100 kV UHVDC converter stations,the arrester configuration scheme and some basic parameters for ±1 100 kV Zhundong converter station are proposed.Overvoltage of equipments in AC system,valve hall,DC busbar,and neutral busbar are also calculated in accordance with the fundamental principles of arrester configuration for UHV converter stations and the existing experiences in insulation coordination of ±800 kV UHVDC converter stations.The work is done also for specifing insulation levels for ±1 100 kV UHVDC converter stations of the ±1 100 kV UHVDC power transmission project from Zhundong to Sichuan in China.Thus,the recommended insulation margins that determine the insulation levels of converter station equipments are proposed: the insulation margins for thyristor valves are 10%/10%/15% for switching impulse/ lightning impulse/ steer front impulse; the insulation levels of lighting and swtiching impulses are recommended as 2 600 kV and 2 150 kV respectively for 1 100 kV DC buses,and as 2 250 kV and 2 100 kV respectively for equipments at the valve side of high-voltage Y/Y converter transformers.
引用
收藏
页码:2477 / 2484
页数:8
相关论文