Influence of Zeotropic Mixtures' Temperature Gliding on the Performance of Heat Transfer in Condenser or Evaporator

被引:3
作者
赵力
高攀
机构
[1] Tianjin 300072
[2] China
[3] School of Mechanical Engineering Tianjin University
基金
中国国家自然科学基金;
关键词
zeotropic mixtures; temperature gliding; exergetic loss; maximum flow rate;
D O I
暂无
中图分类号
TQ051 [化工过程用机械与设备];
学科分类号
080706 ;
摘要
Many zeotropic refrigerant mixtures are proposed as alternatives to some chlorofluorocar-bons (CFCs) and hydrochlorofluorocarbons ( HCFCs). An advantage of zeotropic mixtures is the possibility of reduction in entropy generation by matching the temperature glidings of refrigerant and heat-transfer fluid in both condenser and evaporator. Zeotropic mixtures are compared with pure re-frigerants to evaluate their exergetic losses. On the other hand, the special phenomena which result from temperature gliding are proved by experiments. A simple equation is obtained, to evaluate dif-ferent zeotropic mixtures’ exergetic losses. The maximum flow rate of heat-transfer fluids is found in order that refrigerants phase change can be completed. Lastly, some examples of zeotropic mix-tures ( R407C, R405A and R414B) are given, and their exergetic losses and maximum flow rate of heat-transfer fluids in condenser are forecasted.
引用
收藏
页码:400 / 406
页数:7
相关论文
共 7 条
[1]  
Temperature matching method of selecting working fluids for geo-thermal heat pumps. Zhao P C,Zhao L,Ding G L et al. Applied Thermal Engineer-ing . 2003
[2]  
Comparison experimental analysis between a non-zeotropic mixtures working fluid and R22. Zhao Li. Journal of Chemistry . 2004
[3]  
Application of non-zeotropic mixtures working fluids in refrigera-tor with two doors. Gao Zhiming,Wang Huaixin,Ma Yitai. Journal of Engineering Ther-mophysics . 1996
[4]  
Researches of Working Fluids for Moderate and High Temperature Geothemal Heat Pump and Its Intelligent Controlling. Zhao Li. . 2001
[5]  
Affection of two systematic parameters on the geothermal heat pump system operation. Zhao L,Zhang T J,Zhang Q et al. Renewable Energy . 2003
[6]  
Performance of some zeotropic mixtures as alternative refrigerants to R22 and R502. Venkatarathnam G,Murthy S. International Journal of Energy Research . 1998
[7]  
Experimental evaluation of a new fluid to foe used in heat pump and air conditioning system. Zhao Li,Zhang Qi,Tu Guangbei. Journal of Chemi-cal Industry and Engineering . 2002