山区35kV补偿电网消弧线圈投切运行的暂态分析(英文)

被引:4
作者
袁涛
司马文霞
冉锐
机构
[1] StateKeyLaboratoryofPowerTransmissionEquipment&SystemSecurityandNewTechnology,ChongqingUniversity
关键词
D O I
暂无
中图分类号
TM732 [电力系统的运行];
学科分类号
120103 [信息系统与信息管理];
摘要
Based on a lot of measurement and analysis,this paper find that the unbalanced nature of 35 kV grids due to unsymmetrical capacitance values gives difficulty in neutral point operation in mountainous area.Improving compensation of Petersen coil can rectify imbalance of voltage but bring up new problem that Petersen coil can not extinguish grounding arc effectively in fault.To put down contradiction mentioned above,this paper proposes a combination operation for neutral point of 35 kV grids as neutral point insulated in routine operation and grounding through Petersen coil in fault,then EMTP simulation is carried out.Simulation indicates that new neutral operation method can improve lightning withstand level and decrease trip-out rate of grids.