侧风环境下自然通风湿式冷却塔周向进风变化规律

被引:9
作者
高明 [1 ]
史月涛 [1 ]
王妮妮 [2 ]
孙奉仲 [1 ]
平亚明 [1 ]
机构
[1] 山东大学能源与动力工程学院
[2] 山东电力工程咨询院
关键词
侧风; 湿式冷却塔; 进风; 传热传质性能;
D O I
暂无
中图分类号
TB65 [制冷机械和设备];
学科分类号
0807 ; 080705 ;
摘要
研究了自然通风湿式冷却塔底部周向进风随着外界侧风变化的规律,整个研究在一个热态模型冷却塔试验台上进行.研究表明:无风时,塔底周向进风是均匀轴对称的,即塔内填料各处的传热传质性能也是轴对称分布的.但侧风环境下,外界侧风破坏了冷却塔底部周向进风的轴对称分布规律,侧风风速大于0.2 m/s时各处进风越不均匀.与无风工况相比,当侧风风速为0.5 m/s时,迎风面进风口风速为无风时的1.875倍,而背风面进风口风速仅为无风时的30%.因此,外界侧风影响了进入塔内的总体通风量,恶化了塔内的传热传质性能.
引用
收藏
页码:154 / 158
页数:5
相关论文
共 11 条
[1]   横向风对自然通风干式冷却塔空气流场影响的模型实验研究 [J].
翟志强 ;
朱克勤 ;
符松 .
实验力学, 1997, (02) :142-147
[2]   The effect of the heat exchanger arrangement and wind-break walls on the performance of natural draft dry-cooling towers subjected to cross-winds [J].
duPreez, AF ;
Kroger, DG .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 1995, 58 (03) :293-303
[3]  
A study of the unfavorable effects of wind on thecooling efficiency of dry cooling towers. WEI Q D. Journal of WindEngineering and Industrial Aerodynamics . 1995
[4]  
Astudy on he effects of wind on the air intake flow rate of a cool-ing tower:part 1,wind tunnel study. DERKSEN D D,JBENDER T,BERGSTROM D J,et al. Journal of Wind En-gineering and Industrial Aerodynamics . 1996
[5]  
Astudy on the effects of wind on the air intake flow rate of a cool-ing tower:part 2,wind wall study. DERKSEN D D,JBENDER T,BERGSTROM D J,et al. Journal of Wind Engi-neering and Industrial Aerodynamics . 1996
[6]  
Astudy on the effects of wind on the air intake flow rate of a cool-ing tower:part 3,numerical study. DERKSEN D D,BENDER T,BERGSTROM D J,et al. Journal of Wind Engi-neering and Industrial Aerodynamics . 1996
[7]  
Perfor-mance prediction of wet cooling tower using artificial neuralnetwork under crosswind conditions. GAO Ming,SUN Fengzhong,ZHOU Shoujun,et al. International Journal ofThermal Sciences . 2009
[8]  
Experimentalresearch of heat transfer performance on natural draft counterflow wet cooling tower under crosswind conditions. GAO Ming,SUN Fengzhong,WANG Kai,et al. Interna-tional Journal of Thermal Sciences . 2008
[9]  
The effect of the heat exchanger arrangement and wind-break walls on the performance of natural draft dry-cooling towers subjected to cross-winds. A. F. du Preez,and D. G. Kroger. Journal of Wind Engineering and Industrial Aerodynamics . 1995
[10]  
CFD simulation of wet cool- ing towers. RAFAT A-W,MASUD B. Applied Thermal Engineering . 2006