变压器油中糠醛浓度 ρ(C5H4 O2 )是绝缘纸老化程度的重要指标。实验证实了绝缘纸的拉伸强度与聚合度(DP)呈线性关系 ,ρ(C5H4 O2 )对数值与DP呈负线性关系 ,可使用高性能的液相色谱分析仪测 ρ(C5H4 O2 ) ,以判断绝缘纸的老化程度。水会加快绝缘纸中纤维链的断裂速度 ,而水又是绝缘纸老化过程中的生成物之一 ,故形成了绝缘纸老化的自催化 (正反馈 )过程 ,变压器各部分的温差使老化过程更加复杂。短期内 (几个月 ) ρ(C5H4 O2 )的显著变化表明变压器内部存在隐患并引发故障的概率相当大 ,故定期检测变压器中 ρ(C5H4 O2 )十分必要。
引用
收藏
页码:63 / 64+67 +67
页数:3
相关论文
共 11 条
  • [1] Assessment of transformer insulation condition by evaluation of paper-oil systems. Murthy T S R. Proc IEEE Conference on Electrical Insulation and Dielectric Phenomena, San Francisco . 1996
  • [2] A review of paper ageing in power transformers. Shroff D H and Stannett A W. IEE Proceedings . 1985
  • [3] Astudyofthedegradationofcellulosicinsulationmaterialsinapowertranformer.PartⅢ:Degradationproductsofcelluloseinsulationpaper. HillDJT,,LeTT,DarvenizaMetal. PolymerDegradationandStability . 1996
  • [4] Condition monitoring of pwoer transformers. Domun M K. IEE Colloquium Digest . 1994
  • [5] A study of the degradation of cellulosic insulation materials in a power transformer.Part 1: Molecular weight study of cellulose insulation paper. Hill D J T,Le T T,Darveniza M et al. Polymer Degradation and Stability . 1995
  • [6] Determination of paper degradation by products by direct injection on an HPLC column. Lessard M C,Lamarre C,Gendron A et al. Proc Conf on Electrical Insulation and Dielectric Phenomena, San Francisco . 1995
  • [7] Development of a rapid spectrophotometry method for analysis of furfuraldehyde in transformer oil as an indication of paper ageing. Pahlavanpour B,Duffy G. Proc Conf on Electrical Insulation and Dielectric Phenomena, 1993,Pocona Manor .
  • [8] Infrared detection of transformer insulation degradation due to accelerated ageing. Blue R,Uttamchandani D,Farish O. IEEE Transactions on Dielectrics and Electrical Insulation . 1998
  • [9] Recent advances in the analysis and interpretation of aged insulation from operating power transformers. Allan D M. . 1997
  • [10] Absorption of CO2 and CO gases and furfural in insulating oil into paper insulation in oil-immersed transformers. Kan H et al. Proc IEEE International Symposium on Electrical Insulation, Pittsburg . 1994