全绝缘自支撑电缆系统设计(英文)

被引:1
作者
George G.Karady
Kumaraguru Prabakar
机构
[1] School of Electrical Computer and Energy Engineering
[2] Arizona State University
[3] Tempe
关键词
dry band arcing; all-dielectric self-supporting cable; fiber optic cable; voltage distribution; current distribution; all-dielectric self-supporting circuit simulation;
D O I
10.13336/j.1003-6520.hve.2011.11.015
中图分类号
TM246 [电气装备用电线电缆];
学科分类号
0805 ; 080502 ; 080801 ;
摘要
<正>All-dielectric self-supporting(ADSS) cables are installed along with transmission line for the purpose of communication.During installation the outer layer of the cable is hydrophobic and is not prone to dry band arcing. These cables become less hydrophobic over time and become vulnerable to dry band arcing.This loss in hydrophobicity is because of the contamination formed on the outer layer due to pollution.This is one of the reasons which cause cable failure.Considerable amount of losses will be incurred on the occurrence of a cable failure as the cables are also leased to other companies.An improved equivalent circuit is used to calculate the voltage and current distribution of the double circuit line.A three-phase single circuit line and a three-phase double circuit line are used to calculate their corresponding voltage distribution and current distribution.The results could be used to predict dry band arcing on similar models.The method used considers sag,span and pollution on ADSS cable.
引用
收藏
页码:2715 / 2720
页数:6
相关论文
共 1 条
[1]  
Damages and destruction of fiber optic cables on 161kV overhead transmission lines .2 Kaidanov F,Munteanu R,Sheinfain G. IEEE Electrical Insulation Magazine . 2000