海上风电直流传输网络的成本效益分析(英文)

被引:5
作者
王晟 [1 ]
冯春媚 [2 ]
文安 [3 ]
梁军 [1 ]
机构
[1] Institute of Energy,Cardiff University,Cardiff CF AA,UK
[2] GE Energy,Staffordshire ST TW,UK
[3] China Southern Power Grid
关键词
DC transmission; economics; availability; wind power generation;
D O I
暂无
中图分类号
TM614 [风能发电]; TM711 [网络分析、电力系统分析];
学科分类号
0807 ;
摘要
Due to low load factors of wind power generation,it is possible to reduce transmission capacity to minimize the cost of transmission system construction.Two VSC-HVDC schemes for offshore wind farm,called the point to point(PTP) and DC mesh connections are compared in terms of the utilization of transmission system and its cost.A Weibull distribution is used for estimating offshore wind power generation,besides,the cross correlation between wind farms is considered.The wind energy curtailment is analyzed using the capacity output possibility table(COPT).The system power losses,costs of transmission investment and wind energy curtailment are also computed.A statistic model for the wind generation and transmission is built and simulated in MATLAB to validate the study.It is concluded that a DC mesh transmission can reduce the energy curtailment and power losses.Further benefit is achievable as the wind cross correlation between wind farms decreases.
引用
收藏
页码:36 / 43
页数:8
相关论文
共 2 条
  • [1] Calculation of economic transmission connection capacity for wind power generation .2 Ault G W,Bell K R W,Galloway S J. IET Renewable Power Generation . 2007
  • [2] HVDC grid feasibility study .2 CIGRE B- Working Group. . 2011