Adaptive rotor current control for wind-turbine driven DFIG using resonant controllers in a rotor rotating reference frame

被引:2
作者
Jia-bing HU
机构
关键词
Unbalanced grid voltage; Doubly-fed induction generator (DFIG); Proportional plus Resonant (PR) controller; Fault ride-through (FRT);
D O I
暂无
中图分类号
TM315 [风力发电机];
学科分类号
080801 ;
摘要
This paper proposes an adaptive rotor current controller for doubly-fed induction generator (DFIG), which consists of a proportional (P) controller and two harmonic resonant (R) controllers implemented in the rotor rotating reference frame. The two resonant controllers are tuned at slip frequencies ωslip+ and ωslip-, respectively. As a result, the positive- and negative-sequence components of the rotor current are fully regulated by the PR controller without involving the positive- and negative-sequence decomposition, which in effect improves the fault ride-through (FRT) capability of the DFIG-based wind power generation system during the period of large transient grid voltage unbalance. Correctness of the theoretical analysis and feasibility of the proposed unbalanced control scheme are validated by simulation on a 1.5-MW DFIG wind power generation system.
引用
收藏
页码:149 / 155
页数:7