800kV叠装式瓷绝缘子大雨下的性能评估(英文)

被引:2
作者
Orsino Oliveira Filho [1 ]
Darcy RMello [1 ]
Jos ACardoso [1 ]
Rogrio Mde Azevedo [1 ]
Sylvia GCarvalho [2 ]
Waldenir ASCruz [2 ]
机构
[1] CEPEL Electric Power Research Center AvOlinda s/n Adrianópolis Zip Code - Nova Iguau,RJ,Brazil
[2] FURNAS Rua Real Grandeza, Zip Code - Rio de Janeiro,RJ,Brazil
关键词
porcelain multicone type insulators; flashover voltage tests; dielectric performance under heavy rain;
D O I
10.13336/j.1003-6520.hve.2008.12.032
中图分类号
TM216 [绝缘子和套管];
学科分类号
0805 ; 080502 ; 080801 ;
摘要
An 800 kV electric power substation can have more than one hundred of porcelain multicone type insulators supporting busbar structures.Two or more sections in series,having middle and end fittings,compose these insulators.Ageing process can cause degradation of the cement used in this type of insulator and this fact can affect its dielectric performance under heavy rain.This paper presents results of an investigation based on power frequency high voltage tests performed on 800 kV porcelain multicone type insulators,removed from service after having operated for more than 20 years,as well a non-used one that had been stored on site for long time.The insulators were tested in different arrangements:each section at a time and the two sections assembled in series,as actually used insulator columns.The tests were carried out under artificial rain ranging from 1 mm/min to 5 mm/min.The results have confirmed a reduction of up to 30% in the insulator power frequency flashover voltage under 5 mm/min rain conditions and gave important information to the utility about radial cracks that were observed in many insulators and about the discharge mechanisms along the insulators under rain.
引用
收藏
页码:2552 / 2557
页数:6
相关论文
共 4 条
[1]  
Advances in high voltage engineering. Haddad A,Warne D. IEE Power&Energy Series . 2004
[2]  
Insulation coordination study based on fault initiation and fault clearing overvoltage at the765kVItabera substation. Rogério Mde Azevedo,F MSalgado Carvalho,Orsino O Filho,et al. ICHVE 2008 . 2008
[3]  
Performance evaluation of20years old ZnOsurge ar-resters based on laboratory tests. Orsino Oliveira Filho,Flávio B Barbosa,Rogério Mde Azeve-do,et al. ICHVE 2008 . 2008
[4]  
Cement growth failure mechanism in porcelain suspension insulators. Cherney E A,Hooton R D. IEEE Transactions on Power Delivery . 1987