Equivalence between the load curve and the free-running temperature in energy estimating methods

被引:29
作者
Ghiaus, C [1 ]
机构
[1] Univ La Rochelle, Lab Etudes Phenomenes Transfert Appl Batiment, F-17000 La Rochelle, France
关键词
energy performance; bin methods; degree-day; on-line measurements; BEMS;
D O I
10.1016/j.enbuild.2005.08.003
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The methods used to assess the energy performance of buildings are static or dynamic. A paradigm shift is to estimate the energy consumption by using a probabilistic approach and a single concept for the whole range of operation of the building (heating, ventilation and cooling) and to decouple the thermal behavior of the building, the thermal comfort range and the climate data. These requirements can be achieved by using the free-running temperature to characterize the building behavior and the frequency distribution of the outdoor temperature to describe the climate. This paper demonstrates that the dynamic values can be used to estimate the energy load curve, that this curve may be applied to calculate the energy consumption and that the free-running temperature is an equivalent form of the heating/cooling curve. The main advantages of using the concept of free-running temperature are that: (1) the dynamic behavior may be described by steady-state concepts, (2) the whole range of building operation (heating, ventilation and cooling) is described by a single concept and (3) the thermal behavior of the building, the comfort and the climate are decoupled. The mathematical formalism uses matrix notation. (c) 2005 Elsevier B. V. All rights reserved.
引用
收藏
页码:429 / 435
页数:7
相关论文
共 14 条
[1]  
*ASHRAE, 2001, ASHRAE FUND
[2]  
Elkhuizen P. A., 2003, Building Services Engineering Research & Technology, V24, P191, DOI 10.1191/0143624403bt071oa
[3]   A new simplified thermal design tool for architects [J].
Ellis, MW ;
Mathews, EH .
BUILDING AND ENVIRONMENT, 2001, 36 (09) :1009-1021
[4]  
Germano M, 2005, INT J VENT, V4, P49, DOI [10.1080/14733315.2005.11683698, DOI 10.1080/14733315.2005.11683698]
[5]   Experimental estimation of building energy performance by robust regression [J].
Ghiaus, C .
ENERGY AND BUILDINGS, 2006, 38 (06) :582-587
[6]   Free-running building temperature and HVAC climatic suitability [J].
Ghiaus, C .
ENERGY AND BUILDINGS, 2003, 35 (04) :405-411
[7]   Potential for free-cooling by ventilation [J].
Ghiaus, Cristian ;
Allard, Francis .
SOLAR ENERGY, 2006, 80 (04) :402-413
[8]   Energetic analysis of a passive solar design, incorporated in a courtyard after refurbishment, using an innovative cover component based in a sawtooth roof concept [J].
Heras, MR ;
Jiménez, MJ ;
San Isidro, MJ ;
Zarzalejo, LF ;
Pérez, M .
SOLAR ENERGY, 2005, 78 (01) :85-96
[9]   COMPUTATION OF SYSTEM BALANCING TRANSFORMATIONS AND OTHER APPLICATIONS OF SIMULTANEOUS DIAGONALIZATION ALGORITHMS [J].
LAUB, AJ ;
HEATH, MT ;
PAIGE, CC ;
WARD, RC .
IEEE TRANSACTIONS ON AUTOMATIC CONTROL, 1987, 32 (02) :115-122