Simulation evaluation of the ventilation effect on the performance of a VRV system in cooling mode - Part II, simulation evaluation

被引:29
作者
Aynur, Tolga N. [1 ]
Hwang, Yunho [1 ]
Radermacher, Reinhard [1 ]
机构
[1] Univ Maryland, Ctr Environm Energy Engn, Dept Engn Mech, College Pk, MD 20742 USA
来源
HVAC&R RESEARCH | 2008年 / 14卷 / 05期
关键词
D O I
10.1080/10789669.2008.10391039
中图分类号
O414.1 [热力学];
学科分类号
摘要
The effect of ventilation on indoor temperature control, thermal comfort, outdoor unit energy consumption, and the efficiency of the multisplit variable refrigerant volume (VRV) system is investigated numerically. Similar to experimental results reported in Aynur et al. (2008), ventilation does not affect the indoor temperature control of the multisplit VRV system. However, it increases the energy consumption of the multisplit VRV system. A control strategy for the multisplit VRV system integrated with the heat recovery ventilation (HRV) units' "synchronized indoor fan operation with economizer" is proposed, which promises 17%-28% energy savings when compared with the "continuous indoor fan operation without economizer.
引用
收藏
页码:783 / 795
页数:13
相关论文
共 28 条
[1]  
[Anonymous], 2007, 2007 IEEE POW ENG SO, DOI DOI 10.1109/PES.2007.385645
[2]  
Asiedu Y, 2005, ASHRAE TRAN, V111, P857
[3]   Experimental evaluation of the ventilation effect on the performance of a VRV system in cooling mode - Part I: Experimental evaluation [J].
Aynur, Tolga N. ;
Hwang, Yunho ;
Radermacher, Reinhard .
HVAC&R RESEARCH, 2008, 14 (04) :615-630
[4]   Capacity modulation of an inverter-driven multi-air conditioner using electronic expansion valves [J].
Choi, JM ;
Kim, YC .
ENERGY, 2003, 28 (02) :141-155
[5]  
Dieckmann J, 2003, ASHRAE J, V45, P57
[6]  
*DOE, 2005, ENERGYPLUS ENG DOC V
[7]  
Goetzler W, 2007, ASHRAE J, V49, P24
[8]  
HAI XH, 2006, 11 INT REFR AIR COND, P1
[9]  
Hosni M, 1998, ASHRAE T, V104, P356
[10]  
Hosni M.H., 1999, ASHRAE Transactions, V105, P527