Analysis of Voltage Profile Problems Due to the Penetration of Distributed Generation in Low-Voltage Secondary Distribution Networks

被引:132
作者
Chen, Po-Chen [1 ]
Salcedo, Reynaldo [1 ]
Zhu, Qingcheng [1 ]
de Leon, Francisco [1 ]
Czarkowski, Dariusz [1 ]
Jiang, Zhong-Ping [1 ]
Spitsa, Vitaly [1 ]
Zabar, Zivan [1 ]
Uosef, Resk Ebrahem [2 ]
机构
[1] NYU, Dept Elect & Comp Engn, Polytech Inst, Brooklyn, NY 11201 USA
[2] Consolidated Edison Inc, New York, NY 10003 USA
基金
美国国家科学基金会;
关键词
Distributed generation (DG); low-voltage secondary networks; maximum penetration of DG; voltage quality;
D O I
10.1109/TPWRD.2012.2209684
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a comprehensive analysis of the possible impacts of different penetration levels of distributed generation (DG) on voltage profiles in low-voltage secondary distribution networks. Detailed models of all system components are utilized in a study that performs hundreds of time-domain simulations of large networked distribution systems using the Electromagnetic Transients Program (EMTP). DGs are allocated in a probabilistic fashion to account for the uncertainties of future installations. The main contribution of this paper is the determination of the maximum amount of DG that secondary distribution networks can withstand without exhibiting undervoltage and overvoltage problems or unexpected load disconnections. This information is important for network planning engineers to facilitate the extension of the maximum penetration limit. The results show that depending on the location, type, and size of the installed DGs, small amounts of DG may cause overvoltage problems. However, large amounts of DG may not cause any voltage problems when properly selected.
引用
收藏
页码:2020 / 2028
页数:9
相关论文
共 37 条
[1]  
[Anonymous], 2006, HDB GEN REQ EL SERV
[2]  
[Anonymous], 2003, IEEE STANDARD 1547
[3]  
[Anonymous], EL TRANSM DISTR REF
[4]  
[Anonymous], HDB POWER QUALITY
[5]  
[Anonymous], 2005, C571244 IEEE
[6]  
[Anonymous], 2005, P 18 INT C EXH EL DI
[7]   Method for determining the maximum allowable penetration level of distributed generation without steady-state voltage violations [J].
Ayres, H. M. ;
Freitas, W. ;
De Almeida, M. C. ;
Da Silva, L. C. P. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2010, 4 (04) :495-508
[8]   Reliability evaluation of distributed generation based on operation mode [J].
Bae, In-Su ;
Kim, Jin-O .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (02) :785-790
[9]  
Barker PP, 2000, 2000 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-4, P1645, DOI 10.1109/PESS.2000.868775
[10]  
Begovic M., 2001, System Sciences, P654, DOI DOI 10.1109/HICSS.2001.926265