Performance Analysis and Comparison on Energy Storage Devices for Smart Building Energy Management

被引:172
作者
Xu, Zhanbo [1 ]
Guan, Xiaohong [1 ,2 ]
Jia, Qing-Shan [3 ]
Wu, Jiang [1 ]
Wang, Dai [1 ]
Chen, Siyun [1 ]
机构
[1] Xi An Jiao Tong Univ, Moe Klinns Lab, Xian 710049, Peoples R China
[2] Tsinghua Univ, Ctr Intelligent & Networked Syst CFINS, Dept Automat, TNLIST, Beijing 100084, Peoples R China
[3] Tsinghua Univ, CFINS, TNLIST, Dept Automat, Beijing 100084, Peoples R China
关键词
Building energy saving; mixed integer programming; optimal capacities and types; storage devices;
D O I
10.1109/TSG.2012.2218836
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A smart building energy system usually contains multiple energy sources such as power grids, autonomous generators, renewable resources, storage devices, and schedulable loads. Storage devices such as batteries, ice/heat storage units, and water tanks play an important role in reducing energy cost in building energy systems since they can help sufficiently utilize renewable energy resources and time-of-use electricity prices. It is important to plan, schedule, and coordinate all the storage devices together with schedulable loads in a building facilitated by microgrid technology. To consider the above problem with uncertainties in solar radiation and demand profiles, a stochastic optimization problem is formulated and solved by the scenario tree method. The best combination and the optimal capacities of storage devices for specific building energy systems are then determined. Furthermore, the optimal operating strategy of building energy systems can be obtained. The performance analysis on the storage devices is conducted and the numerical results show that thermal storage devices (e. g., ice storage units, water tanks) are good for saving energy costs but batteries may not be economical due to their high investment cost and short lifetime. It is also observed that the aforementioned uncertainties have an impact on selecting which type and capacity of storage device should be used.
引用
收藏
页码:2136 / 2147
页数:12
相关论文
共 15 条
[1]  
[Anonymous], 2007, DEV UNIT DEST TSINGH
[2]  
Braun J. E., 1992, ASHRAE
[3]   Energy-Efficient Buildings Facilitated by Microgrid [J].
Guan, Xiaohong ;
Xu, Zhanbo ;
Jia, Qing-Shan .
IEEE TRANSACTIONS ON SMART GRID, 2010, 1 (03) :243-252
[4]   Generating scenario trees for multistage decision problems [J].
Hoyland, K ;
Wallace, SW .
MANAGEMENT SCIENCE, 2001, 47 (02) :295-307
[5]  
Huang Y., 2006, Impact of climate change on the energy use of the residential and commercial building sectors
[6]  
Lai Z., 2009, THESIS TSINGHUA U BE
[7]  
Li X., 2007, HV AC, V37, P83
[8]   Optimal technology selection and operation of commercial-building microgrids [J].
Marnay, Chris ;
Venkataramanan, Giri ;
Stadler, Michael ;
Siddiqui, Afzal S. ;
Firestone, Ryan ;
Chandran, Bala .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (03) :975-982
[9]  
Moongilan D., 2009, PROC IEEE S PRODUCT, P1
[10]  
SIDDIQUI A, 2005, DISTRIBUTED GENERATI