Reliability assessment of distribution system with the integration of renewable distributed generation

被引:174
作者
Adefarati, T. [1 ]
Bansal, R. C. [1 ]
机构
[1] Univ Pretoria, Dept Elect Elect & Comp Engn, ZA-0002 Pretoria, South Africa
关键词
Distributed generation; Distribution system; Hybrid system; Photovoltaic system; Reliability assessment; Energy storage system; Wind turbine generator; ENERGY-STORAGE SYSTEMS; POWER-SYSTEM; DISTRIBUTION NETWORKS; ADEQUACY ASSESSMENT; WEATHER CONDITIONS; WIND POWER; PV SYSTEMS; OPTIMIZATION; COST; METHODOLOGY;
D O I
10.1016/j.apenergy.2016.10.087
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
080707 [能源环境工程]; 082001 [油气井工程];
摘要
Recent studies have shown that renewable energy resources will contribute substantially to future energy generation owing to the rapid depletion of fossil fuels. Wind and solar energy resources are major sources of renewable energy that have the ability to reduce the energy crisis and the greenhouse gases emitted by the conventional power plants. Reliability assessment is one of the key indicators to measure the impact of the renewable distributed generation (DG) units in the distribution networks and to minimize the cost that is associated with power outage. This paper presents a comprehensive reliability assessment of the distribution system that satisfies the consumer load requirements with the penetration of wind turbine generator (WTG), electric storage system (ESS) and photovoltaic (PV). A Markov model is proposed to access the stochastic characteristics of the major components of the renewable DG resources as well as their influence on the reliability of a conventional distribution system. The results obtained from the case studies have demonstrated the effectiveness of using WTG, ESS and PV to enhance the reliability of the conventional distribution system. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:158 / 171
页数:14
相关论文
共 58 条
[1]
Considering cost and reliability in electrical and thermal distribution networks reinforcement planning [J].
Abbasi, Ali Reza ;
Seifi, Ali Reza .
ENERGY, 2015, 84 :25-35
[2]
Integration of renewable distributed generators into the distribution system: a review [J].
Adefarati, T. ;
Bansal, R. C. .
IET RENEWABLE POWER GENERATION, 2016, 10 (07) :873-884
[3]
Reliability Assessment of 4.2 MW Single Shaft Typhoon Gas Fired Turbine Power Generation Station (2003-2008) [J].
Adegboye, B. A. ;
Ekundayo, K. R. .
ADVANCES IN MATERIALS AND SYSTEMS TECHNOLOGIES III, 2012, 367 :143-150
[4]
A New Procedure in Reliability Assessment of Wind-Diesel Islanded Grids [J].
Aghaebrahimi, M. R. ;
Mehdizadeh, M. .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2011, 39 (14) :1563-1576
[5]
A novel approach for optimal combinations of wind, PV, and energy storage system in diesel-free isolated communities [J].
Ahadi, Amir ;
Kang, Sang-Kyun ;
Lee, Jang-Ho .
APPLIED ENERGY, 2016, 170 :101-115
[6]
Al-Muhaini M, P IEEE C POW EN SOC
[7]
Evaluating Future Power Distribution System Reliability Including Distributed Generation [J].
Al-Muhaini, Mohammad ;
Heydt, Gerald T. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (04) :2264-2272
[8]
Alkuhayli AA, P IEEE N AM POW S NA, P1
[9]
A RELIABILITY TEST SYSTEM FOR EDUCATIONAL PURPOSES - BASIC DISTRIBUTION-SYSTEM DATA AND RESULTS [J].
ALLAN, RN ;
BILLINTON, R ;
SJARIEF, I ;
GOEL, L ;
SO, KS .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1991, 6 (02) :813-820
[10]
EVALUATION OF RELIABILITY INDEXES AND OUTAGE COSTS IN DISTRIBUTION-SYSTEMS [J].
ALLAN, RN ;
DASILVA, MG .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (01) :413-419