An approach to management of critical indoor air problems in school buildings

被引:34
作者
Haverinen, U
Husman, T
Toivola, M
Suonketo, J
Pentti, M
Lindberg, R
Leinonen, J
Hyvärinen, A
Meklin, T
Nevalainen, A
机构
[1] Natl Publ Hlth Inst, Lab Environm Microbiol, FIN-70701 Kuopio, Finland
[2] Natl Publ Hlth Inst, Epidemiol Unit, FIN-70701 Kuopio, Finland
[3] Tampere Univ Technol, Lab Struct Engn, FIN-33101 Tampere, Finland
关键词
asthma; health effects; moisture damages; mold; questionnaire; respiratory symptoms;
D O I
10.1289/ehp.99107s3509
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This study was conducted in a school center that had been the focus of intense public concern over 2 years because of suspected mold and health problems. Because several attempts to find solutions to the problem within the community were not satisfactory, outside specialists were needed for support in solving the problem. The study group consisted of experts in civil engineering, indoor mycology, and epidemiology. The studies were conducted in close cooperation with the city administration. Structures at risk were opened, moisture and temperature were measured, and the causes of damage were analyzed. Microbial samples were taken from the air, surfaces, and materials. Health questionnaires were sent to the schoolchildren and personnel. Information on the measurements and their results was released regularly to school employees, students and their parents, and to the media. Repairs were designed on the basis of this information. Moisture damage was caused mainly by difficult moisture conditions at the building site, poor ventilation, and water leaks. Fungal genera (concentrations <200 colony-forming units (cfu)/m(3), <3000 cfu/cm(2)) typical to buildings with mold problems (e.g., Aspergillus versicolor, Eurotium) were collected from the indoor air and surfaces of the school buildings. Where moisture-prone structures were identified and visible signs of damage or elevated moisture content were recorded, the numbers of microbes also were high; thus microbial results from material samples supported the conclusions made in the structural studies. Several irritative and recurrent symptoms were common among the upper secondary and high school students. The prevalence of asthma was high (13%) among the upper secondary school students. During the last 4 years, the incidence of asthma was 3-fold that of the previous 4-year period.
引用
收藏
页码:509 / 514
页数:6
相关论文
共 18 条
[1]   ASSOCIATIONS BETWEEN QUESTIONNAIRE REPORTS OF HOME DAMPNESS AND CHILDHOOD RESPIRATORY SYMPTOMS [J].
BRUNEKREEF, B .
SCIENCE OF THE TOTAL ENVIRONMENT, 1992, 127 (1-2) :79-89
[2]   INDOOR AIR-QUALITY AND HEALTH - REPRODUCIBILITY OF RESPIRATORY SYMPTOMS AND REPORTED HOME DAMPNESS AND MOLDS USING A SELF-ADMINISTERED QUESTIONNAIRE [J].
DALES, RE ;
SCHWEITZER, I ;
BARTLETT, S ;
RAIZENNE, M ;
BURNETT, R .
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 1994, 4 (01) :2-7
[3]  
FLANNIGAN B, 1996, CONTROL MOISTURE PRO
[4]  
Husman T, 1996, SCAND J WORK ENV HEA, V22, P5, DOI 10.5271/sjweh.103
[5]  
HUSMAN T, 1995, THESIS U HELSINKI HE
[6]  
Hyvarinen A., 1993, INDOOR AIR, V3, P337, DOI DOI 10.1111/J.1600-0668.1993.00017.X
[7]   RESPIRATORY SYMPTOMS AND INFECTIONS AMONG CHILDREN IN A DAY-CARE-CENTER WITH MOLD PROBLEMS [J].
KOSKINEN, O ;
HUSMAN, T ;
HYVARINEN, A ;
REPONEN, T ;
NEVALAINEN, A .
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 1995, 5 (01) :3-9
[8]  
MEKLIN T, 1996, P 7 INT C IND AIR QU, V2, P1083
[9]  
*MIN ENV HOUS BUIL, 1997, ENV GUID, V28
[10]  
*MIN SOC AFF HLTH, 1997, GUID IND AIR QUAL