Estimating substation peaks from load research data

被引:51
作者
Broadwater, RP
Sargent, A
Yarali, A
Shaalan, HE
Nazarko, J
机构
[1] ARKANSAS POWER & LIGHT, HOT SPRINGS, AR USA
[2] BIALYSTOK TECH UNIV, DEPT ELECT ENGN, BIALYSTOK, POLAND
关键词
load estimation; substation peak; load research;
D O I
10.1109/61.568270
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Load research data is used to develop kWh-to-peak-kW conversion factors, diversity factors, and average time-varying load data as a function of customer class, month, and type of day. A new method, Nonlinear Load Research based Estimation (NLRE), is used to derive monthly load shapes by customer class for estimating the peak MW load on substations as a function of total MWh usage by customer class, type of day, and month. Four substations at Hot Springs, Arkansas are used for estimation of monthly peak and the results are compared with measured values from a SCADA system. The results show improved accuracy of the NLRE estimated substation peaks in comparison with the previous method.
引用
收藏
页码:451 / 456
页数:6
相关论文
共 5 条
[1]  
ANDERSON A, 1991, MODEL LOAD SIMULATIO
[2]  
KUO HC, 1993, IEEE T POWER DEL OCT, V8
[3]  
NAZARKO J, 1993, MODELING ELECT POWER
[4]   ESTIMATION OF DIVERSITY AND KWHR-TO-PEAK-KW FACTORS FROM LOAD RESEARCH DATA [J].
SARGENT, A ;
BROADWATER, RP ;
THOMPSON, JC ;
NAZARKO, J .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1994, 9 (03) :1450-1450
[5]  
*WEST CORP, 1965, EL UT ENG REF BOOK D, V3