High Wind Power Penetration in Isolated Power Systems-Assessment of Wind Inertial and Primary Frequency Responses

被引:206
作者
Wang, Ye [1 ]
Delille, Gauthier [1 ]
Bayem, Herman [1 ]
Guillaud, Xavier [2 ,3 ]
Francois, Bruno [2 ,3 ]
机构
[1] EDF R&D, EFESE Dept, F-92141 Clamart, France
[2] Univ Lille Nord France, F-59000 Lille, France
[3] ECLille, L2EP, F-59650 Villeneuve Dascq, France
关键词
Droop controller; frequency response; inertial response; isolated power systems; primary frequency control; rate of change of power; FED INDUCTION GENERATORS; TURBINE GENERATORS; SUPPORT; ENERGY; IMPACT;
D O I
10.1109/TPWRS.2013.2240466
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Grid operational challenges are significant to increase securely the wind penetration level. New embedded control functions are therefore required in order to make participate wind generators in power system management. In this paper the implementation of inertial response and primary frequency control in a wind turbine controller are investigated. Main factors affecting the performances of the frequency regulation are identified and characterized. The influence of control parameters and the turbine operating point on the inertial response are analyzed through obtained performances in an islanded power system. The combined control scheme using both controllers is also developed and the potential of the obtained grid service at partial load is discussed.
引用
收藏
页码:2412 / 2420
页数:9
相关论文
共 27 条
[1]  
[Anonymous], MODELING GE WIND TUR
[2]  
[Anonymous], 2011, EIRGRID GRID COD V3
[3]  
[Anonymous], P INT WORKSH JUNCT T
[4]  
Brisebois J, 2011, IEEE POW ENER SOC GE
[5]   Frequency response capability of full converter wind turbine generators in comparison to conventional generation [J].
Conroy, James F. ;
Watson, Rick .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (02) :649-656
[6]   Participation of doubly fed induction wind generators in system frequency regulation [J].
de Almeida, Rogerio G. ;
Pecas Lopes, J. A. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (03) :944-950
[7]  
Delille G, 2010, IEEE PES INNOV SMART
[8]   Dynamic Frequency Control Support by Energy Storage to Reduce the Impact of Wind and Solar Generation on Isolated Power System's Inertia [J].
Delille, Gauthier ;
Francois, Bruno ;
Malarange, Gilles .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2012, 3 (04) :931-939
[9]   Comparison of the response of doubly fed and fixed-speed induction generator wind turbines to changes in network frequency [J].
Ekanayake, J ;
Jenkins, N .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2004, 19 (04) :800-802
[10]   Control of DFIG wind turbines [J].
Ekanayake, J ;
Holdsworth, L ;
Jenkins, N .
POWER ENGINEER, 2003, 17 (01) :28-32