Active Filter for the Removal of the DC Current Component for Single-Phase Power Lines

被引:36
作者
Buticchi, Giampaolo [1 ]
Consolini, Luca [1 ]
Lorenzani, Emilio [2 ]
机构
[1] DII Univ Parma, I-43100 Parma, Italy
[2] DISMI Univ Modena & Reggio Emilia, I-42122 Reggio Emilia, Italy
关键词
Active filters; distributed power; nonlinear systems; power grids; power system measurements; power transformers; static power converters; TRANSFORMERLESS; COMPENSATION; INVERTER; DESIGN;
D O I
10.1109/TIE.2012.2213562
中图分类号
TP [自动化技术、计算机技术];
学科分类号
080201 [机械制造及其自动化];
摘要
Nonlinear loads and grid-connected converters can cause, in addition to the generation of several current harmonics in the grid current, a dc current component injection. A dc current component can cause the magnetic core saturation of distribution power transformers. Transformers operating under saturation conditions present increased power losses, overheating, and distorted current waveforms. Since a dc current component causes a small dc voltage component drop across the parasitic resistance of the distribution grid conductors, canceling the dc voltage component at the point of common coupling (PCC) implies the compensation of the dc current component injected/absorbed by electric loads or grid-connected converters connected at the same PCC. This paper proposes a low-cost nonlinear sensor for an accurate detection, free from offset problems, of the dc voltage component present in the grid voltage. The detection of the dc voltage component was used to realize an active filter of the dc current component. The proposed solution is outlined, and then the stability issue is addressed by means of a simplified model. Experimental results confirmed that the simplified model closely approximates the real system.
引用
收藏
页码:4403 / 4414
页数:12
相关论文
共 23 条
[1]
[Anonymous], 2005, EPE 2005
[2]
Auto-calibrating dc link current sensing technique for transformerless, grid connected, H-bridge inverter systems [J].
Armstrong, Matthew ;
Atkinson, David. J. ;
Johnson, C. Mark ;
Abeyasekera, Tusitha. D. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2006, 21 (05) :1385-1393
[3]
A Shunt Active Power Filter With Enhanced Performance Using ANN-Based Predictive and Adaptive Controllers [J].
Bhattacharya, Avik ;
Chakraborty, Chandan .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (02) :421-428
[4]
Approach to low-cost prevention of DC injection in transformerless grid connected inverters [J].
Blewitt, W. M. ;
Atkinson, D. J. ;
Kelly, J. ;
Lakin, R. A. .
IET POWER ELECTRONICS, 2010, 3 (01) :111-119
[5]
Direct current offset controller for transformerless single-phase photovoltaic grid-connected inverters [J].
Bowtell, L. ;
Ahfock, A. .
IET RENEWABLE POWER GENERATION, 2010, 4 (05) :428-437
[6]
Buticchi G., 2010, IECON 2010 - 36th Annual Conference of IEEE Industrial Electronics, P3244, DOI 10.1109/IECON.2010.5675334
[7]
A DC Offset Current Compensation Strategy in Transformerless Grid-Connected Power Converters [J].
Buticchi, Giampaolo ;
Lorenzani, Emilio ;
Franceschini, Giovanni .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) :2743-2751
[8]
Online Optimal Reactive Power Control Strategy of PV Inverters [J].
Cagnano, Alessia ;
De Tuglie, Enrico ;
Liserre, Marco ;
Mastromauro, Rosa A. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (10) :4549-4558
[9]
Current Harmonic Compensation by a Single-Phase Shunt Active Power Filter Controlled by Adaptive Neural Filtering [J].
Cirrincione, Maurizio ;
Pucci, Marcello ;
Vitale, Gianpaolo ;
Miraoui, Abdellatif .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2009, 56 (08) :3128-3143
[10]
Enders W., 2001, P 17 EUR PHOT SOL EN